![ABB ACS550 Series Скачать руководство пользователя страница 191](http://html.mh-extra.com/html/abb/acs550-series/acs550-series_user-manual_334191.webp)
ACS550 User’s Manual
191
Embedded fieldbus
• To reduce noise on the network, terminate the RS485 network using 120
Ω
resistors at both ends of the network. Use the DIP switch to connect or disconnect
the termination resistors. See following diagram and table.
• Connect the shield at each end of the cable to a drive. On one end, connect the
shield to terminal 28, and on the other end connect to terminal 32. Do not connect
the incoming and outgoing cable shields to the same terminals, as that would
make the shielding continuous.
• For configuration information see the following sections:
–
–
Activate drive control functions – EFB
on page
– The appropriate EFB protocol specific technical data. For example,
Communication set-up – EFB
Serial communication selection
To activate the serial communication, set parameter 9802
COMM
PROT
SEL
=
1 (
STD MODBUS
).
Note:
If you cannot see the desired selection on the panel, your drive does not have
that protocol software in the application memory.
X1
Identification
Hardware description
28
Screen
29
B (Po)
30
A (Negative -)
31
AGND
32
Screen
Terminated
Terminated
station
Station
Station
station
28 SCR
29 B
30 A
31 AGND
32 SCR
SCR
+
-
GND
RS485 Multidrop application
RS485 interface
Bus termination
OFF position
ON position
SCR
+
-
GND
J2
ON
J2
ON
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...