![ABB ACS550 Series Скачать руководство пользователя страница 78](http://html.mh-extra.com/html/abb/acs550-series/acs550-series_user-manual_334078.webp)
78
ACS550 User’s Manual
Application macros
PFC macro
This macro provides parameter settings for pump and fan control (PFC) applications.
To enable, set the value of parameter 9902 to 7 (
PFC
CONTROL
).
Note:
Parameter 2108
START
INHIBIT
must remain in the default setting, 0 (
OFF
).
Connection example:
Input signals
Output signals
Jumper setting
• Analog ref. and actual (AI1, 2)
• Start/stop – manual/PFC (DI1, 6)
• Run enable (DI2)
• EXT1/EXT2 selection (DI3)
• Interlock (DI4, 5)
• Analog output AO1: Frequency
• Analog output AO2: Actual 1
• Relay output 1: Running
• Relay output 2: Fault (-1)
• Relay output 3: Aux. motor ON
or
Note:
Use the following switch-on order:
1. EXT1/EXT2
2. Run Enable
3. Start.
EXT1/EXT2 selection:
Activation selects PFC control
1 SCR
2 AI1
3 AGND
4 10V
5 AI2
6 AGND
7 AO1
8 AO2
9 AGND
10 24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
Start/Stop (Manual):
Activation starts the drive
Start/Stop (PFC):
Activation starts the drive
Run enable:
Deactivation always stops the drive
External ref. 1 (Manual) or Ext ref. 2 (PID/PFC):
0
…
10 V
1
Reference voltage 10 V DC
Output frequency:
0
…
20 mA
Actual 1 (PI controller actual value):
0(4)
…
20 mA
Analog input circuit common
Analog output circuit common
Auxiliary voltage 24 V DC
Auxiliary voltage output common
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
Actual signal (PID):
4
…
20 mA
Interlock:
Deactivation always stops the drive
Interlock:
Deactivation stops constant speed motor
Note 1.
Manual: 0
…
10V => 0
…
50 Hz
PID/PFC: 0
…
10V => 0
…
100%
PID setpoint
Relay output 1, programmable
Default operation:
Relay output 2, programmable
Default operation:
Relay output 3, programmable
Default operation:
Running
=>19 connected to 21
Fault (-1)
=>22 connected to 24 (Fault => 22 connected to 23)
Auxiliary motor switched on
=>25 connected to 27
2
Note 2.
The sensor needs to be powered.
See the manufacturer’s instructions.
A connection example of a two-wire
sensor is shown on page
X1
1…10 kohm
J1
AI1: 0
…
10 V
AI2: 0(4)
…
20 mA
ON
ON
AI1: 0
…
10 V
AI2: 0(4)
…
20 mA
ON
12
J1
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...