Figure 37. SFC Display with Expanded Step
SFC Display Operation
Section 4 TCL Displays
88
3BUR002418-600 A
Transitions are shown beneath the activities and conditions window for a step. There
are two types of transition windows. If a transition contains a GOTO which
addresses the next step in the TCL sequence, it is displayed with the step number
and step text beneath the tic mark on the main program flow line. Transitions which
refer to other steps or which do not have GOTO actions are displayed in the
expanded step area. If a GOTO is present, the step number is displayed on a button
following the transition tic mark. Use the horizontal scroll bar to see additional
transitions, if necessary.
Activities and conditions can have both load text and runtime text. The load text is
displayed when the sequence is first loaded. It is replaced by runtime text as that
part of the sequence is executed. Load text describes what should happen during
execution of the sequence; runtime text describes what actually happens. Transitions
only have load text. Each transition has two load texts (one for each button).
SFC Display Operation
Activities
Step activities specify the actions that will be performed in each program step.
Activities are highlighted to illustrate the degree of execution of the program (the
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Страница 2: ......
Страница 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Страница 14: ...Table of Contents 14 3BUR002418 600 A ...
Страница 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Страница 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Страница 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Страница 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Страница 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Страница 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Страница 330: ...Index 330 3BUR002418 600 A ...
Страница 331: ......