PID Controller FCM
Appendix A Runtime Templates
236
3BUR002418-600 A
BAD INPUTS ACCEPTED Field
This field specifies whether an input with BAD data quality is treated as if the data
quality is GOOD. Valid entries are:
NO
do not accept bad inputs
YES
accept bad inputs
ACTION ON BAD INPUT Field
This field specifies the action to take if the controller input signal goes to BAD data
quality. Valid entries are:
FCM OFF
controller FCM is turned off
MAN OUT controller FCM goes to the Manual output mode
NONE
FCM continues processing according to its configuration
ACTION ON BAD SETPT Field
This field specifies the action to take if the setpoint signal goes to a BAD data
quality. Valid entries are:
NONE
no special action is taken
MAN OUT output mode is switched to Manual
LOC SPT
setpoint mode goes to Local
FCM OFF
FCM is turned off
SETPOINT RETURN MODE Field
This field specifies the setpoint mode to enter when the mode returns from Track.
Valid entries are:
PREVIOUS go to the mode active before the setpoint went to Track
LOCAL
go to the Local mode
REMOTE
go to the Remote mode
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Страница 2: ......
Страница 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Страница 14: ...Table of Contents 14 3BUR002418 600 A ...
Страница 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Страница 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Страница 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Страница 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Страница 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Страница 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Страница 330: ...Index 330 3BUR002418 600 A ...
Страница 331: ......