Appendix A Runtime Templates
Device Loop Templet
3BUR002418-600 A
223
Valid entry is:
a decimal number identifying which bits are inverted. See the description of the
INVERTED INPUTS field for an example of inverting bits.
TRANSITION OVERRIDE Field
A transition timeout occurs when the system issues a command to a device and the
device does not go to the proper state within the time specified by the TIMER field.
The TRANSITION OVERRIDE field specifies the action applied to the device
command (DEV_CMND) when a transition timeout occurs.
Valid entries are:
NONE
no change
STATE
set to entry in the DEVICE STATE field (DEV_STAT). If
STATE is specified, but the current state does not correspond
to a valid command, the action taken is the entry in the SAFE
COMMAND field, if a command is specified in that field.
SAFE CMD
action taken is the entry in the SAFE COMMAND field
PREVIOUS CMD
set to the last successful previous command
SPECIAL CMD
set to command specified in the SPECIAL COMMAND field
LOOP STATE Field
This field determines whether the loop is processed. When LOOP STATE is OFF,
the loop processor ignores the loop. The configuration entry is the initial loop state
for the loop.
Valid entries are:
ON
process the loop
OFF
do not process the loop
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Страница 2: ......
Страница 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Страница 14: ...Table of Contents 14 3BUR002418 600 A ...
Страница 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Страница 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Страница 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Страница 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Страница 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Страница 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Страница 330: ...Index 330 3BUR002418 600 A ...
Страница 331: ......