Adaptive Gain
Appendix A Runtime Templates
248
3BUR002418-600 A
OUTPUT LOWER FACTOR Field
This field specifies the multiplier of the base gain or reset associated with the lower
breakpoint, BP1, of the output adaptive function. Valid entry is a decimal value.
PROCESS HIGH LIMIT Field
This field specifies the maximum allowed value for the process adaptive
contribution to the overall gain or reset. Valid entry is a decimal number.
PROCESS LOW LIMIT Field
This field specifies the minimum allowed value for the process adaptive
contribution to the overall gain or reset. Valid entry is low limit value.
PROCESS UPPER BRKPT Field
This field specifies the upper breakpoint, BP2, for the process adaptive function.
The gain or reset starts to change when the size of the process variable becomes
greater than the upper breakpoint. Valid entry is a decimal value in percent.
PROCESS LOWER BRKPT Field
This field specifies the lower breakpoint, BP1, for the process adaptive function.
The gain or reset changes when the process variable becomes less than the lower
breakpoint. Valid entry is a decimal value in percent.
PROCESS UPPER FACTOR Field
This field specifies the multiplier of the base gain or reset associated with the upper
breakpoint, BP2, of the process adaptive function. Valid entry is a decimal value.
PROCESS LOWER FACTOR Field
This field specifies the multiplier of the base gain or reset associated with the lower
breakpoint, BP1, of the process adaptive function. Valid entry is a decimal value.
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Страница 2: ......
Страница 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Страница 14: ...Table of Contents 14 3BUR002418 600 A ...
Страница 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Страница 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Страница 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Страница 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Страница 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Страница 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Страница 330: ...Index 330 3BUR002418 600 A ...
Страница 331: ......