TRIO LAN Display
Section 7 I/O Displays
184
3BUR002418-600 A
Use
Restart Bus
if the CI560 TRIO MIB submodule does not come up as expected
after a controller reboot or to restart a failed Field Bus Controller.
Use
Switch Bus
to force a switchover of all blocks using the selected ACTIVE bus
with redundancy AVAILABLE to the other bus.
TRIO Blocks on the Field Bus
Each block on the Field Bus is represented by a row on the TRIO LAN Display. To
select a TRIO Block Display, move the cursor to the row for the block and click.
The block column has either the block number in red or the background in red to
indicate the block has an active diagnostic message. The following information is
displayed for each block:
Block
The first cell in a row contains the block number, 1 to 30, for the
block on the bus. This number is displayed as follows for the
indicated conditions:
Red = diagnostic(s) active
Black = no diagnostics active
On the AC Controller, if this cell has a black
background, you can use the context menu to
get the
Switch Bus
command (background is
red if diagnostic is active). Using Switch Bus
here switches only those blocks associated with the BSM (a single
stub) providing redundancy is AVAILABLE.You will be asked to
Confirm or Cancel the switch bus request.
Also on the AC Controller, the letter A or B after the number
indicates which bus the block is using. If the block is FAILED, then
a ? replaces the bus letter.
Templet
This cell contains either the name of the block templet or NOT
CONFIGURED if no block templet exists.
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Страница 2: ......
Страница 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Страница 14: ...Table of Contents 14 3BUR002418 600 A ...
Страница 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Страница 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Страница 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Страница 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Страница 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Страница 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Страница 330: ...Index 330 3BUR002418 600 A ...
Страница 331: ......