Real Compare FCM
Appendix A Runtime Templates
272
3BUR002418-600 A
0
1
0
1
0
1
1
1
0
where
prev is the value of the result from the previous sample period
any non-zero input is treated as a 1
As long as inp2 (Reset) is 0, the result goes to 1 as soon as inp1 (Set) goes to 1. The
result remains at 1 regardless of the subsequent state of inp1. When inp2 goes to 1,
the result is forced to 0, and remains there as long as inp2 is 1.
Real Compare FCM
This FCM compares two analog signals and provides a logical output if a specified
condition is met.
COMPENSATION CONSTANT Field
This field specifies the comparison constant, when INPUT SOURCE 2 is not
specified. Valid entry is any number.
COMPARE OPERATOR Field
This field specifies the operator for the comparison constant. Valid entries are:
EQ
equal to
NE
not equal to
GT
greater than
GE
greater than or equal to
LT
less than
LE
less than or equal to
NORMAL STATE Field
This field specifies the normal state of the FCM's result. Valid entries are: 0, 1
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Страница 2: ......
Страница 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Страница 14: ...Table of Contents 14 3BUR002418 600 A ...
Страница 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Страница 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Страница 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Страница 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Страница 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Страница 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Страница 330: ...Index 330 3BUR002418 600 A ...
Страница 331: ......