Device Loop Templet
Appendix A Runtime Templates
224
3BUR002418-600 A
ALARM PRIORITY Field
This field specifies the priority level for any alarms occurring for the device.
Valid entries are:
HIGH
high (priority 1)
MED
medium (priority 2)
STD
standard (priority 3)
POSTING ENABLE Field
This field indicates whether posting is enabled for the loop. Posting affects the way
alarm information is presented at the Operator Stations or Multibus-based consoles
and on the Alarm/Event Log.
Valid entries are:
YES
enable posting
NO
disable posting
SUPPRESS ALARMS Field
This field specifies whether the loop processor checks to see if the alarms defined by
this loop are active.
Valid entries are:
YES
suppress alarms (do not check)
NO
do not suppress alarms
DEVICE OVERRIDE Field
This field overrides the feedback timer. When set to YES, there are no Timeout
Alarms for the device. See the description of the TIMER field for a description of
Timeout Alarms.
Valid entries are:
NO_CHECK
override the feedback timer
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Страница 2: ......
Страница 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Страница 14: ...Table of Contents 14 3BUR002418 600 A ...
Страница 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Страница 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Страница 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Страница 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Страница 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Страница 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Страница 330: ...Index 330 3BUR002418 600 A ...
Страница 331: ......