DO810
Appendix A Runtime Templates
312
3BUR002418-600 A
The default value is 0 (zero)
.
Examples from above:
All with No Supervision
hex number =
205A0000
converted to decimal =
542769152
All with Supervision
hex number =
205A000F
converted to decimal =
542769167
Channels 4 and 1 with Supervision
hex number =
205A0009
converted to decimal =
542769161
Channels 3 and 2 with Supervision
hex number = 205A0006
converted to decimal =
542769158
Channels 2 and 1 with Supervision
hex number =
205A0003
converted to decimal =
542769155
VALUE CYCLE TIME
Enter the channel value update period (msec) over the fieldbus. Refer to
S800 I/O
User’s Guide
for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096.
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Страница 2: ......
Страница 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Страница 14: ...Table of Contents 14 3BUR002418 600 A ...
Страница 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Страница 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Страница 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Страница 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Страница 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Страница 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Страница 330: ...Index 330 3BUR002418 600 A ...
Страница 331: ......