ELECTRICAL CONNECTIONS
NOTE:
Disconnect all poles until all work has been completed
and fuse prior to re-connecting! The connection of the
sauna control unit must be completed by a licensed
specialist (electrician) in accordance with the relevant
standards. The cable used must comply with the
relevant statutory provisions.
NOTE:
According to standard EN60335, light and oven have to
have a separate power supply.
Since the sauna control unit is powered via the light
supply, it is crucial that the light supply is connected!
6.1.0
TERMINAL OVERVIEW
Minimum cross section in mm
2
(copper)
Connected load
in kW
Supply
conductor
Heater line
System
fusing
Evaporator
Exhauster
7,5
5 x 2,5
5 x 1,5
3 x 16 A
3 x 1,5
3 x 1,5
9
5 x 2,5
5 x 1,5
3 x 16 A
3 x 1,5
3 x 1,5
12
1
5 x 2,5
5 x 1,5
2 x 16 A, 1 x
20 A
3 x 1,5
3 x 1,5
18
2
5 x 4,0
5 x 4,0
3 x 32 A
3 x 1,5
3 x 1,5
1
Only with special wiring usable!
2
Only with power extension!
page 20 of 32