132 / 138
Identification: MD-AL-GI-00
Rev. 1.1 of 15/03/2021 - Application: GID
User’s Manual 3PH 50000TL-60000TL-V1
Rev. 1.1 15/03/2021
Datalogger SIDE
SENSOR SIDE
V1
terminal
(12Vdc output voltage)
RED +12V
Terminal
GND
terminal
(GND/RTN)
BLACK 0V
Terminal
V2
terminal
(12Vdc driveable voltage)
Table 4: Electrical connection of the sensor to the datalogger (power supply)
A stable communication in terms of signal and power supply, up to 200m, is guaranteed by using the RS485
cable, type Te.Co. 15166 (2x2x0,22+1x0,22)st/pu.
For longer distances, a connection to the signal side of the datalogger is recommended, and a connection to
the +12V power supply via an external power supply unit.
10.4.8.
Configuring the Datalogger
Connect to the website dlconfig.it and login by entering the temporary credentials: Username = admin and
Password = admin.
In the screen that opens, enter the serial number(S/N) of the datalogger to be configured and click
“SEARCH”.