58 / 138
Identification: MD-AL-GI-00
Rev. 1.1 of 15/03/2021 - Application: GID
User’s Manual 3PH 50000TL-60000TL-V1
Rev. 1.1 15/03/2021
Check ON-OFF
Select “5. Contr On-Off” and press “OK” to enter the menu for setting the remote control switch. The display
will show “Enter PWD!” Press “OK” to enter the password “0001” using the “Up” and “Down” keys to select
the number and “OK” to move to the next digit. If the display shows “Incorrect, try again!” press the “Back”
key and enter the password again. When the password has been entered correctly, you can enter the menu.
Use the “Up” and “Down” keys to select the “1.Enable” or “2.Disable” option and select it with the “OK” key. If
the “Enable” option is selected, you will then need to indicate how many days you want to keep the inverter
switched off using the Up and Down keys, and confirming with OK. After setting the “Enable” option, contact
the installer to obtain the password for restarting the inverter.
Relay command
Select “6. Relay Command” and press “OK” to enter the menu for setting the relay command. Use the “Up”
and “Down” keys to select the respective configuration items, as shown below. Press “OK” to select them. If
the setting is successful, “OK” will be displayed; otherwise, “Error” will be displayed.
6. Relay command
1. Production
2. Alarm
3. Alarm config
4. Disab Relay
Below is a detailed definition of the configurations that can be set:
Production
The relay changes over whenever it detects a connection to (or
disconnection from) the grid.
If the relay contact is normally open (or closed), the relay will remain
open (or closed) until the inverter is connected to the grid; when the
inverter connects to the grid and starts feeding power, the relay
changes over and then closes (or opens).
When the inverter disconnects from the grid, the relay contact returns
to its standard position, i.e. open (or closed).
Alarm
The relay switches over whenever there is an alarm on the inverter
(Error). No changeover occurs in the event of a temporary alarm.
If the relay contact is normally open (or closed), the relay remains
open (or closed) until the inverter detects an error; if the inverter
detects an error, the relay changes state and therefore closes (or
opens). The contact remains active with respect to its standard