The 3PH 50000TL-60000TL-V1 inverters are three-phase output inverters that comply fully with the local
grid connection requirements and safety standards.
The inverters are equipped with AC output connectors with IP66 protection suitable for photovoltaic use;
customers must provide their own AC output cable connections.
Cable connection procedure
1)
Open the front cover on the bottom of the inverter by removing the six grub screws.
Figure 27 - Connecting the AC output cables (1)
2)
Identify the suitable cable section as shown in the table and remove an appropriate length of the
protective sheath, as shown in the figure. Then insert the AC output cable through the waterproof cable
gland.
Figure 28 - Connecting the AC output cables (2)
3)
Connect the AC power cable according to the following criteria and as shown in the figure:
•
Connect the yellow-green (ground) cable to the terminal labelled “PE”, tighten the wire using a
screwdriver;
•
Connect the phase R cable to the terminal labelled “R”, tighten the wire using a screwdriver;