UFR1002IP
12690-0701-00
Seite
31 / 50
www.ziehl.de
Germany VDE-AR-N4105:
Generator, Pn
2011
2018
≤ 50 kW
> 50 kW
3AC +
3AC +
3AC +
3AC +
My
3AC+N
1AC+N
3AC+N
3AC+N 3AC+N
Data
230 V
230 V
230 V
230 V
230 V
Main
Sub
Parameter
Pr1.01
Pr1.07
Pr1.02
Pr1.08
Pr1.09
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ver. 00
U0
Alarm active
no
no
no
no
59v0
Alarm on
[V]
46,0
46,0
46,0
46,0
Alarm off
[V]
36,0
36,0
36,0
36,0
Delay alarm on [s]
1,50
1,50
1,50
1,50
Delay alarm off [s]
60
60
60
60
Display U0/UM> [s]
5,0
5,0
5,0
5,0
F
requ
ency
f >>
Alarm active
no
no
no
81.S2
Alarm on
[Hz]
52,50
52,50
52,50
81>S2
Alarm off
[Hz]
50,10
50,10
50,10
Delay alarm on [s]
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
f >
Alarm active
yes
yes
yes
yes
yes
81.S1
Alarm on
Hz
51,50
51,50
51,50
51,50
51,50
81>S1
Alarm off
Hz
50,05
50,05
50,10
50,10
50,10
Delay alarm on [s]
0,10
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
60
f <
Alarm active
yes
yes
yes
yes
yes
81.S1
Alarm on
[Hz]
47,50
47,50
47,50
47,50
47,50
81<S1
Alarm off
[Hz]
48,50
48,50
47,60
47,60
47,60
Delay alarm on [s]
0,10
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
60
f <<
Alarm active
no
no
no
81.S2
Alarm on
[Hz]
47,00
47,00
47,00
81<S2
Alarm off
[Hz]
47,60
47,60
47,60
Delay alarm on [s]
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
f/U< protect Alarm active
no
no
no
no
no
U< Limit
[V]
46,0
46,0
46,0
46,0
46,0
Frequency- Alarm active
range
Alarm U< on
[V]
Alarm U< off
[V]
Alarm 3U0 on
[V]
Alarm 3U0 off
[V]
Delay alarm on [s]
Delay alarm off [s]
V
ec
to
r
shif
t
Alarm active
no
no
no
no
no
VSR deg
°
10,0
10,0
10,0
10,0
10,0
Delay alarm off [s]
3
3
3
3
3
suppression
[s]
2
2
2
2
2
RO
CO
F
Alarm active
no
no
no
no
no
df / dt
0,800
0,800
2,000
2,000
2,000
Periods
20
20
20
20
20
Delay alarm on [s]
0,10
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
60
F
ee
d
-
b
ac
k
Feedback at
Y1+Y2
Y1+Y2
Y1
Y1
Y1
Time for feedb. [s]
5,0
5,0
5,0
5,0
5,0
Reclosing
attempts
2
2
2
2
2
Reclosing Time [s]
5
5
5
5
5
Pr1.02, Pr1.08, Pr1.09:
- Code lock ex works activated
- Blue values -> parameters that can be changed with code lock