UFR1002IP
12690-0701-00
Seite
40 / 50
www.ziehl.de
Offtria
Switzerland
Belgium
United Kingdom
TOR
NE/EEA
Erzeuger
Typ A-D
NE7
CH2020
C10/11
G98 (G83/2) + G99 (G59/3)
My
3AC+N
3AC +
3AC+N
3AC+N
3AC+N
3AC
3AC+N
3AC
Data
230 V
230 V
230 V
230 V
400 V
63,5 V
110 V
Main
Sub
Parameter
Pr1.10
Pr1.15
Pr1.16
Pr1.20
Pr1.21
Pr1.22
Pr1.23
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ver. 00
U0
Alarm active
no
no
no
no
no
no
no
59v0
Alarm on
[V]
46,0
46,0
46,0
46,0
80,0
46,0
80,0
Alarm off
[V]
36,0
36,0
36,0
36,0
70,0
36,0
70,0
Delay alarm on [s]
1,50
1,50
1,50
1,50
1,50
1,50
1,50
Delay alarm off [s]
60
60
1
60
60
60
60
Display U0/UM> [s]
5,0
5,0
5,0
5,0
5,0
5,0
5,0
F
requ
ency
f >>
Alarm active
no
no
no
yes
yes
yes
yes
81.S2
Alarm on
[Hz]
51,50
51,50
50,30
52,00
52,00
52,00
52,00
81>S2
Alarm off
[Hz]
50,10
50,10
50,10
50,05
50,05
50,05
50,05
Delay alarm on [s]
0,10
0,10
0,05
0,50
0,50
0,50
0,50
Delay alarm off [s]
60
60
1
20
20
20
20
f >
Alarm active
yes
yes
yes
no
no
no
no
81.S1
Alarm on
Hz
51,50
51,50
51,50
51,50
51,50
51,50
51,50
81>S1
Alarm off
Hz
50,10
50,10
50,10
50,05
50,05
50,05
50,05
Delay alarm on [s]
0,10
0,10
0,05
90,00
90,00
90,00
90,00
Delay alarm off [s]
60
60
1
20
20
20
20
f <
Alarm active
yes
yes
yes
yes
yes
yes
yes
81.S1
Alarm on
[Hz]
47,50
47,50
47,50
47,50
47,50
47,50
47,50
81<S1
Alarm off
[Hz]
47,60
47,60
49,90
48,50
48,50
48,50
48,50
Delay alarm on [s]
0,10
0,10
0,05
20,00
20,00
20,00
20,00
Delay alarm off [s]
60
60
1
20
20
20
20
f <<
Alarm active
no
no
no
yes
yes
yes
yes
81.S2
Alarm on
[Hz]
47,50
47,50
49,70
47,00
47,00
47,00
47,00
81<S2
Alarm off
[Hz]
47,60
47,60
49,90
48,00
48,00
48,00
48,00
Delay alarm on [s]
0,10
0,10
0,05
0,50
0,50
0,50
0,50
Delay alarm off [s]
60
60
1
20
20
20
20
f/U< protect Alarm active
no
no
no
no
no
no
no
U< Limit
[V]
46,0
161,0
20,0
46,0
46,0
20,0
20,0
Frequency- Alarm active
no
range
Alarm U< on
[V]
196,0
Alarm U< off
[V]
199,0
Alarm 3U0 on
[V]
11,5
Alarm 3U0 off
[V]
10,5
Delay alarm on [s]
0,05
Delay alarm off [s]
1
V
ec
to
r
shif
t
Alarm active
no
no
no
no
no
no
no
VSR deg
°
10,0
10,0
7,0
50,0
50,0
50,0
50,0
Delay alarm off [s]
60
3
20
20
20
20
20
suppression
[s]
2
2
2
2
2
2
2
RO
CO
F
Alarm active
no
no
yes
yes
yes
yes
yes
df / dt
0,800
2,000
1,000
1,000
1,000
1,000
1,000
Periods
20
20
8
20
20
20
20
Delay alarm on [s]
0,10
0,10
0,20
0,50
0,50
0,50
0,50
Delay alarm off [s]
60
60
1
20
20
20
20
F
ee
d
-
ba
ck
Feedback at
off
Y1
off
off
off
off
off
Time for feedb. [s]
1,5
5,0
1,5
1,5
1,5
1,5
1,5
Reclosing
attempts
2
2
2
2
2
2
2
Reclosing Time [s]
5
5
5
5
5
5
5