UFR1002IP
12690-0701-00
Seite
42 / 50
www.ziehl.de
15.5 SFS-EN50549-1+2:2019 + EN50549-1 2-stage + NEN-EN50549-1:2019 + VDE 0126 VFR2019
When changing the program, all parameters are reset.
Finland
Ireland
Netherlands France
SFS-EN50549-
1+2:2019
EN50549-1
2-stage
NEN-
EN50549-
1:2019
VDE
0126
VFR2019
My
3AC+N
3AC
3AC+N
3AC
3AC+N
3AC+N
Data
230 V
400 V
230 V
400 V
230 V
230 V
Main
Sub
Parameter
Pr1.30
Pr1.31
Pr1.32
Pr1.33
Pr1.34
Pr1.36
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ma
ins
con
n
e
c
-t
ion
Connection
3AC-N
3AC
3AC-N
3AC
3AC-N
3AC-N
Nominal voltage [V]
230,0
400,0
230,0
400,0
230,0
230,0
Coupling device
no
no
no
no
no
no
S
w
it
ch o
n
con
d
it
ion
s
Voltage
Active
no
no
no
no
no
no
U max.
[V]
253,0
438,0
264,0
463,0
253,0
261,0
U min.
[V]
195,5
337,9
196,0
337,0
195,5
187,0
Frequency Active
no
no
no
no
no
no
F max.
[Hz]
51,00
51,00
50,15
50,15
50,10
50,05
F min.
[Hz]
49,00
49,00
47,90
47,90
48,50
48,50
Switch on
delay
Time
[s]
60
60
20
20
60
60
After
alarms
Switch back
triggered triggered triggered triggered
triggered
triggered
Short alarm Active
V
o
lt
age
U >>
Alarm active
no
no
yes
yes
yes
yes
59.S2
Alarm on
[V]
276,0
478,0
281,0
488,0
276,0
264,0
59>S2
Alarm off
[V]
253,0
438,0
276,0
483,0
253,0
261,0
Delay alarm on [s]
1,00
1,00
0,70
0,70
0,10
0,10
Delay alarm off [s]
60
60
20
20
60
60
U >
Alarm active
yes
yes
yes
yes
no
no
59.S1
Alarm on
[V]
276,0
478,0
269,0
468,0
253,0
249,0
59>S1
Alarm off
[V]
253,0
438,0
264,0
463,0
250,0
246,0
Delay alarm on [s]
1,00
1,00
70,00
70,00
0,20
60,00
Delay alarm off [s]
60
60
20
20
60
60
UM>
Alarm active
yes
yes
no
no
yes
no
59-Av
Alarm on
[V]
253,0
438,0
262,0
456,0
253,0
253,0
Alarm off
[V]
250,0
433,0
257,0
451,0
250,0
250,0
Delay alarm on [s]
0,10
0,10
1,00
70,00
0,20
0,10
Delay alarm off [s]
60
60
20
20
60
60
U <
Alarm active
yes
yes
yes
yes
yes
yes
27.S1
Alarm on
[V]
184,0
318,0
191,0
332,0
184,0
184,0
27<S1
Alarm off
[V]
195,5
337,9
196,0
337,0
195,5
187,0
Delay alarm on [s]
1,50
1,50
0,70
0,70
3,00
2,70
Delay alarm off [s]
60
60
20
20
60
60
U <<
Alarm active
yes
yes
no
no
yes
no
27.S2
Alarm on
[V]
46,0
79,7
184,0
320,0
69,0
104,0
27<S2
Alarm off
[V]
195,5
259,7
189,0
325,0
195,5
106,0
Delay alarm on [s]
0,25
0,25
2,50
2,50
0,10
0,30
Delay alarm off [s]
60
60
20
20
60
60
Grey values can only be read (not changed) regardless of the code lock/sealing.