UFR1002IP
12690-0701-00
Seite
18 / 50
www.ziehl.de
8.9 Code lock
The parameters set (including simulation) can be protected using the code lock.
On the website:
Code protected parameters are marked with a
⌨︎
.
Switch the "System" -> "Code lock" page on/off
The old/new pin is requested. if necessary. Apply changes by clicking the "Save" button.
On the device:
When the code lock is active, a "Code lock" message appears when you try to change a parameter.
•
Call up the "Settings" -> "Code lock" menu
•
Switch code lock on/off
•
When the code lock is changed, the previously set pin must always be entered
→
Factory default codepin = 504
→
Forgot your codepin? Switch the device off and on again, keeping the joystick up button pressed (↑) until
"Reset" appears on the display. Select cod
e lock and reset to factory default by pressing „
→“
•
Switch on code lock: Enter new codepin and save by pressing
✔
8.10 Sealing
The parameters set (including simulation) can be locked by means of the sealing.
On the website:
Sealed parameters are marked with a
🔓︎
.
On the device:
If sealing is active, a "Sealing" message appears when an attempt is made to change a parameter.
•
Sealing/locking ON (OFF) setting procedure
→
If present, remove the seal (only by an authorized person)
→
Lift the button cover slightly and turn it 180°
→
Press the button by pressing very firmly on the button cover (the lock in the top right hand
corner of the display will start to flash), keep the button pressed
→
The colour changes from red to green (green = sealing off)
→
The colour changes from green to red (red = sealing active)
→
Release button
→
Apply new sealing if necessary
8.11 Simulation
Comprehensive simulation functions are available to test the correct functioning of the device.
The simulation can be carried out via the web interface or directly on the device.
Web interface: "Home" page -> "Start simulation" button
Device:
“Test/Simulation” menu
•
Simulation relay
→
Access on the device: Menu "Test/Simulation" -> "Start relay"
→
Relays can be individually switched on/off
•
Simulation of measured values
→
Access on the device: Menu "Test/Simulation" -> "Start simulation"
→
Voltage (U), frequency (F) and vector shift (VS) can be simulated