UFR1002IP
12690-0701-00
Seite
36 / 50
www.ziehl.de
15.3 VDE-AR-N 4110:2018-11 + VDE-AR-N 4120:2018-11
When changing the program, all parameters are reset.
Germany
VDE-AR-N4110:2018 +
VDE-AR-N4120:2018
My
3AC+N
3AC
3AC+N
3AC
Data
57,7 V
100 V
230 V
400 V
Main
Sub
Parameter
Pr1.11
Pr1.12
Pr1.13
Pr1.14
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ma
ins
con
n
e
c
-t
ion
Connection
3AC-N
3AC
3AC-N
3AC
Nominal voltage [V]
57,7
100,0
230,0
400,0
Coupling device
no
no
no
no
S
w
it
ch o
n
con
d
it
ion
s
Voltage
Active
no
no
yes
yes
U max.
[V]
63,5
110,0
253,0
440,0
U min.
[V]
51,9
90,0
207,0
360,0
Frequency Active
no
no
yes
yes
F max.
[Hz]
50,20
50,20
50,20
50,20
F min.
[Hz]
47,50
47,50
47,50
47,50
Switch on
delay
Time
[s]
60
60
60
60
After
alarms
Switch back
triggered triggered
all
F+U<+U<<
all
F+U<+U<<
Short alarm Active
V
o
lt
age
U >>
Alarm active
yes
yes
yes
yes
59.S2
Alarm on
[V]
69,2
120,0
287,0
498,0
59>S2
Alarm off
[V]
68,2
119,0
284,0
495,0
Delay alarm on [s]
0,30
0,30
0,10
0,10
Delay alarm off [s]
60
60
60
60
U >
Alarm active
yes
yes
no
no
59.S1
Alarm on
[V]
63,5
110,0
249,0
430,0
59>S1
Alarm off
[V]
62,5
109,0
246,0
427,0
Delay alarm on [s]
180,00
180,00
60,00
60,00
Delay alarm off [s]
60
60
60
60
UM>
Alarm active
no
no
no
no
59-Av
Alarm on
[V]
63,5
110,0
253,0
438,0
Alarm off
[V]
62,5
109,0
250,0
435,0
Delay alarm on [s]
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
U <
Alarm active
yes
yes
yes
yes
27.S1
Alarm on
[V]
46,2
80,0
184,0
318,0
27<S1
Alarm off
[V]
55,2
95,5
219,0
379,0
Delay alarm on [s]
2,70
2,70
1,00
1,00
Delay alarm off [s]
60
60
60
60
U <<
Alarm active
no
no
yes
yes
27.S2
Alarm on
[V]
26,0
45,0
104,0
179,0
27<S2
Alarm off
[V]
55,0
95,0
219,0
359,0
Delay alarm on [s]
0,30
0,30
0,30
0,30
Delay alarm off [s]
60
60
60
60
Grey values can only be read (not changed) regardless of the code lock/sealing.