UFR1002IP
12690-0701-00
Seite
48 / 50
www.ziehl.de
15.7 With coupling device VG1200 - VDE-AR-N 4110:2018-11 + VDE-AR-N 4120:2018-11
When changing the program, all parameters are reset.
Germany
VDE-AR-N4110:2018 +
VDE-AR-N4120:2018
My
3AC
3AC
3AC
Data
690 V
800 V
1000 V
Main
Sub
Parameter
Pr2.00
Pr2.01
Pr2.02
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ma
ins
con
n
e
c
-t
ion
Connection
3AC
3AC
3AC
Nominal voltage [V]
690
800
1000
Coupling device
yes
yes
yes
S
w
it
ch o
n
con
d
it
ion
s
Voltage
Active
yes
yes
yes
U max.
[V]
759
880
1100
U min.
[V]
621
720
900
Frequency Active
yes
yes
yes
F max.
[Hz]
50,20
50,20
50,20
F min.
[Hz]
47,50
47,50
47,50
Switch on
delay
Time
[s]
60
60
60
After
alarms
Switch back
all
F+U<+U<<
all
F+U<+U<<
all
F+U<+U<<
Short alarm Active
V
o
lt
age
U >>
Alarm active
yes
yes
yes
59.S2
Alarm on
[V]
859
996
1245
59>S2
Alarm off
[V]
854
990
1238
Delay alarm on [s]
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
U >
Alarm active
no
no
no
59.S1
Alarm on
[V]
742
860
1075
59>S1
Alarm off
[V]
737
854
1067
Delay alarm on [s]
60,00
60,00
60,00
Delay alarm off [s]
60
60
60
UM>
Alarm active
no
no
no
59-Av
Alarm on
[V]
756
876
1095
Alarm off
[V]
751
870
1088
Delay alarm on [s]
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
U <
Alarm active
yes
yes
yes
27.S1
Alarm on
[V]
549
636
795
27<S1
Alarm off
[V]
654
758
947
Delay alarm on [s]
1,00
1,00
1,00
Delay alarm off [s]
60
60
60
U <<
Alarm active
yes
yes
yes
27.S2
Alarm on
[V]
309
358
448
27<S2
Alarm off
[V]
619
718
898
Delay alarm on [s]
0,30
0,30
0,30
Delay alarm off [s]
60
60
60
Grey values can only be read (not changed) regardless of the code lock/sealing.