UFR1002IP
12690-0701-00
Seite
37 / 50
www.ziehl.de
Germany
VDE-AR-N4110:2018 +
VDE-AR-N4120:2018
My
3AC+N
3AC
3AC+N
3AC
Data
57,7 V
100 V
230 V
400 V
Main
Sub
Parameter
Pr1.11
Pr1.12
Pr1.13
Pr1.14
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ver. 00
U0
Alarm active
no
no
no
no
59v0
Alarm on
[V]
46,0
80,0
46,0
80,0
Alarm off
[V]
36,0
70,0
36,0
70,0
Delay alarm on [s]
1,50
1,50
1,50
1,50
Delay alarm off [s]
60
60
60
60
Display U0/UM> [s]
5,0
5,0
5,0
5,0
F
requ
ency
f >>
Alarm active
no
no
yes
yes
81.S2
Alarm on
[Hz]
51,50
51,50
52,50
52,50
81>S2
Alarm off
[Hz]
50,10
50,10
50,10
50,10
Delay alarm on [s]
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
f >
Alarm active
no
no
yes
yes
81.S1
Alarm on
Hz
51,50
51,50
51,50
51,50
81>S1
Alarm off
Hz
50,10
50,10
50,10
50,10
Delay alarm on [s]
5,40
5,40
5,00
5,00
Delay alarm off [s]
60
60
60
60
f <
Alarm active
no
no
yes
yes
81.S1
Alarm on
[Hz]
47,50
47,50
47,50
47,50
81<S1
Alarm off
[Hz]
49,90
49,90
49,90
49,90
Delay alarm on [s]
0,40
0,40
0,10
0,10
Delay alarm off [s]
60
60
60
60
f <<
Alarm active
no
no
no
no
81.S2
Alarm on
[Hz]
47,50
47,50
47,50
47,50
81<S2
Alarm off
[Hz]
49,90
49,90
49,90
49,90
Delay alarm on [s]
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
f/U< protect Alarm active
no
no
no
no
U< Limit
[V]
20,0
20,0
46,0
46,0
Frequency- Alarm active
range
Alarm U< on
[V]
Alarm U< off
[V]
Alarm 3U0 on
[V]
Alarm 3U0 off
[V]
Delay alarm on [s]
Delay alarm off [s]
V
ec
to
r
shif
t
Alarm active
no
no
no
no
VSR deg
°
10,0
10,0
10,0
10,0
Delay alarm off [s]
3
3
3
3
suppression
[s]
3
3
3
3
RO
CO
F
Alarm active
no
no
no
no
df / dt
2,000
2,000
2,000
2,000
Periods
20
20
20
20
Delay alarm on [s]
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
F
ee
d
-
b
ac
k
Feedback at
off
off
off
off
Time for feedb. [s]
1,5
1,5
1,5
1,5
Reclosing
attempts
2
2
2
2
Reclosing Time [s]
5
5
5
5