UFR1002IP
12690-0701-00
Seite
33 / 50
www.ziehl.de
15.2 BDEW
When changing the program, all parameters are reset.
Germany
BDEW
My
3AC+N
3AC
3AC+N
3AC
Data
57,7 V
100 V
230 V
400 V
Main
Sub
Parameter
Pr1.03
Pr1.04
Pr1.05
Pr1.06
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ma
ins
con
n
e
c
-t
ion
Connection
3AC-N
3AC
3AC-N
3AC
Nominal voltage [V]
57,7
100,0
230,0
400,0
Coupling device
no
no
no
no
S
w
it
ch o
n
con
d
it
ion
s
Voltage
Active
no
no
no
no
U max.
[V]
61,3
107,0
246,0
427,0
U min.
[V]
47,2
81,0
187,0
321,0
Frequency Active
no
no
no
no
F max.
[Hz]
50,05
50,05
50,05
50,05
F min.
[Hz]
48,50
48,50
48,50
48,50
Switch on
delay
Time
[s]
60
60
60
60
After
alarms
Switch back
triggered triggered triggered triggered
Short alarm Active
V
o
lt
age
U >>
Alarm active
yes
yes
yes
yes
59.S2
Alarm on
[V]
66,4
115,0
264,0
458,0
59>S2
Alarm off
[V]
65,4
114,0
261,0
455,0
Delay alarm on [s]
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
U >
Alarm active
yes
yes
yes
yes
59.S1
Alarm on
[V]
62,3
108,0
249,0
430,0
59>S1
Alarm off
[V]
61,3
107,0
246,0
427,0
Delay alarm on [s]
60,00
60,00
60,00
60,00
Delay alarm off [s]
60
60
60
60
UM>
Alarm active
no
no
no
no
59-Av
Alarm on
[V]
63,5
110,0
253,0
438,0
Alarm off
[V]
62,5
109,0
250,0
435,0
Delay alarm on [s]
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
U <
Alarm active
yes
yes
yes
yes
27.S1
Alarm on
[V]
46,2
80,0
184,0
318,0
27<S1
Alarm off
[V]
47,2
81,0
187,0
321,0
Delay alarm on [s]
2,70
2,70
2,70
2,70
Delay alarm off [s]
60
60
60
60
U <<
Alarm active
no
no
no
no
27.S2
Alarm on
[V]
26,0
45,0
104,0
180,0
27<S2
Alarm off
[V]
27,0
46,0
106,0
182,0
Delay alarm on [s]
0,30
0,30
0,30
0,30
Delay alarm off [s]
60
60
60
60
Grey values can only be read (not changed) regardless of the code lock/sealing.