UFR1002IP
12690-0701-00
Seite
15 / 50
www.ziehl.de
Main Menu
Submenu
Parameter menu
Parameter description
Relay K3
Relay function
- Duration on:
K3 static ON
(after time "K3 to K1+K2")
- Pulse on:
K3 for time "K3 pulse" on
(after time "K3 to K1+K2")
- K1=K2=K3:
K3 switches on synchronously with K1/K2
- in case of error:
K3 on when an error occurs
- Life contact.:
K3 off when an error occurs
- Start signal:
If the limit value is exceeded, K3
switches from U >>, U >, U <, U << without delay
- Enable signal:
K3 on when K1+K2 on and reset
pressed (Up 2s key, or ext. Reset to In1…In3)
K3 pulse
Pulse duration of K3,
➔
only visible if "Pulse on" is selected
K3 after K1 + K2
K3 picks up at this time after K1 + K2 with a delay,
➔
only visible if "Pulse on"/"Duration on" is selected
Digital Inputs
Off with E1-E2
Type
➔
Switch off the system with E1-E2: NC / NO
In1
Type
TYPE Input +U-Inx: NC / NO
Function:
• off (function off)
•
Y1 inactive (Y1 evaluation off)
•
Y2 inactive (Y2 evaluation off)
•
Y1+Y2 inactive (Y1 and Y2 evaluations off)
•
VSR inactive (alarm vector shift
off)
•
Release signal (external reset)
Function
In2
Type
Function
In3
Type
Function
Network
DHCP
Ethernet network configuration:
DHCP on: Automatically secure network configuration
from a DHCP server
DHCP off: manual network configuration
IP address
Subnet mask
Gateway
DNS server
MAC address
Settings
Language
➔
Device language:
German / English
Date
➔
Date from real time clock
Time
➔
Time from real time clock
Display interval
➔
Interval at which measured values are updated on
the device display
Brightness
➔
Brightness of the display is turned down after
dimming time without a button being pressed
Dimming time
Factory setting
➔
Reset device to factory default
Code lock
➔
Code lock:
on / off
When the code lock is changed, the previously set pin
must always be entered,
Factory default Codepin = 504.
Forgot your codepin? Switch the device off and on
again, keeping the joystick up button pressed (
↑
) until
"Reset" appears on the display. Select code lock and
reset to factory default with → key.
Test/simulation
Relay
➔
Simulation relay
Simulation
➔
Simulation voltage, frequency and vector shift
Test K1/K2
➔
Measure shutdown times of K1->Y1 and K2-Y2
Switch back time
Reset time
➔
Set all "Delayed alarm off" of voltage and frequency
alarms together
Info
Firmware version
➔
Firmware versions installed on the device
o
Master Firmware
o
Slave Firmware
o
Boot loader
Serial number
➔
Device serial number
Operating hours
➔
Number of operating hours of the device
Comment
➔
Comment can only be written via website