9.7
Menu group Start
Main menu
Start
Start
Settings
Protocol
Base setup
Controller Setup
Start
Motor
In this menu point the modulation for the motor can be switched on and off (ON / OFF).
Factory setting to
|
OFF
|
, this prevents the system from inadvertently starting up before
con
fi
guration is complete.
When operating with two control circuits, the switch-off affects both outputs, i.e. the
inverter output of control circuit 1 and the signal output 0 - 10 V of control circuit 2 .
Attention!
The ON/OFF key affects the following function
Multifunction - LC display and
keyboard!
No disconnection (isolation) when switched off, in accordance with VBG4
§
6)!
OFF
Motor
Start
PIN input
The service menu for the installation can be protected against unintentional changes
by a pin code. With further pin codes putting back to pre-setting is possible.
PIN 0010
Opening service menu, if PIN-protection activated.
PIN 1234
Opening
“
setting
”
.
if
“
set protection
”
=
“
ON
”
(
Controller Setup)
PIN 9090
Restore user setting.
PIN 9091
Save user setting (corresponds function
“
Save user setup
”
=
“
ON
”
Controller Setup)
PIN 9095
Restore factory setting = delivery status
Exception:
The stored events in the
“
Protocol
”
menu are retained after resetting to factory setting!
- - - - -
PIN input
Start
Language
Menu language by the factory set to English.
In this menu different national languages can be selected (GB = English, D = German
...).
GB
Language
US Einheiten
The display can be switched between SI units and imperial (US) units =>US units ON.
SI units (factory setting):
°
C, bar, Pa, m
3
/h, K-Factor, m/s
Imperial (US) units:
°
F , psi, in.wg, cfm, K-Faktor US, ft/s
Settings for temperature differences (with SI units in K) are also made for Imperial units
(US) in
°
F (
Δ
1.8
°
F
Δ
1 K).
Conversion factors:
•
Temperature: t /
°
F = 1,8 x t
°
C + 32.
•
Pressure: 1.0 psi = 0.069 bar, 1.0 in.wg = 254 Pa
•
Air
fl
ow: 1.0 cfm = 0.5885 m
3
/h, inlet ring: K-Factor US = 9.3 x K-Factor SI
•
Speed: 1.0 ft/s = 0.3048 m/s
In order to refresh the display, the desired mode must be con
fi
rmed again after switch-
ing over the units (
Base setup)!
OFF
US Einheiten
Start
Reset
Complete re-start of the device
OFF
Reset
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
53/123