9.10.2.11
Reset, Function
|
10D
|
Reset via an external push-button in case of a motor fault or a malfunction of the controller.
Example for reset after a motor fault
Reset after motor fault by using an non-locking reset key. The unit switches off when interruption between both
“
TB/TP
”
or
“
TK/PTC
”
terminals, the unit then remains switched off
“
motor fault
”
see (
motor protection). Re-
starting after the drive has cooled down (terminals
“
TB/TP
”
- or
“
TK/PTC
”
bridged) by non-locking reset key
possible.
Contact at digital input e.g.
“
Digital In 1
”
For
“
D1 Inverting
”
=
“
OFF
”
both terminals
“
D1
”
-
“
D1
”
in normal operation interrupted. Reset
after fault by short close.(For
“
Inverting
”
=
“
ON
”
reverse function).
9.10.2.12
Setting Max. Speed ON / OFF function
|
11D
|
The value for
“
Max Speed
”
adjusted in menu
“
Settings
”
, is activated over a digital input. I.e. the unit
works independently of the controller function
fi
rm with this value.
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
This function in
fl
uences both circuits in operation with two control circuits.
15.05.2009
v_11d_max_drehzahl.vsd
Controller
24V
D1 D1
= 80 %
1
0
- - - - -
1
0
= 0 .. 100 %
1
Display depending on device type in: %, Hz, rpm
1
Setting
“
Max. Speed
”
or
“
1.Max. Speed
”
and
“
2.Max. Speed
”
for
operation with two control circuits
•
“
D1 Inverting
”
=
“
OFF
”
:
“
Max. Speed
”
active at closed contact
•
“
D1 Inverting
”
=
“
ON
”
:
“
Max. Speed
”
active
at opened contact
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
74/123