9.6
Air velocity control
6.01
9.6.1
Base setup
6.01
Main menu
Base setup
Start
Setting
Protocol
Base setup
Controller Setup
Base setup
Mode
Mode selection
6.01
6.01
Mode
Base setup
E1 Analog In
The sensor input is factory set for mode
6.01
to sensor type
“
MAL1
”
.
Measuring range: 0...1 m/s
Output signal: 0 - 10 V
Connection terminals:
“
E1
”
,
“
GND
”
,
“
24V
”
Other settable sensors / measuring ranges:
•
MAL10 (0...10 m/s, output signal 0 - 10 V)
•
MAL15 * (0...15 m/s, output signal 0 - 10 V)
•
MAL20 * (0...20 m/s, output signal 0 - 10 V)
•
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
order to display the actual value correctly.
Example 0 - 10 V sensor and measuring range 0 - 5 M/s:
E1 Analog In = 0 - 10 V, E1 Unit = m/s, E1 Decimals = 1, E1 Min. = 0,0 m/s, E1 Max. =
5 m/s
* Alternative measuring ranges which can be selected by jumpers for sensor type
MAL10.
MAL1
E1 Analog In
Base setup
E1 Offset
Sensor calibration with calibrated comparison device.
The current
“
E1 Actual
”
is displayed including the offset set here.
0.00 m/s
E1 Offset
Base setup
Adjustable
“
E2 Function
”
•
|
1E
|
= external setpoint e.g. by external signal (0 - 10 V) instead of setting
“
Setpoint
1
”
. 0 - 10 V
0 - 100 % sensor measuring range.
•
|
2E
|
= External manual operation via external signal (0 - 10 V). Switch over
between settings on the device and external manual operation via digital input (
IO Setup: function
|
7D
|
).
•
|
3E
|
= Sensor average to E1
•
|
4E
|
= Sensor comparison to E1
•
|
5E
|
= Sensor difference to E1
•
|
6E
|
= sensor for outdoor temperature-dependent setpoint adaptation, pre-
programmed sensor type
“
TF..
”
.
–
Menu group
“
Setting
”
additional parameter: T-Band, T-Start SA, Min. Setpoint.
–
Menu group
“
Info
”
additional parameter: Setpoint control
–
Example
Setting for operation
4.01
...
4.03
/ additional menu items.
•
|
7E
|
= Measurement value = Measurement value e.g. for limit indication, display in
Info menu
“
E2 Actual
”
.
•
|
8E
|
...
|
13E
|
= sensor input for control circuit 2
base setup / operation
with second control circuit.
OFF
E2 Function
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
51/123