Function
Description function D1..D5
Max. Speed
(11D)
Setting Max. Speed
“
ON
”
/
“
OFF
”
In
fl
uences the respectively set value
“
1. Max. Speed
”
and
“
2. Max. Speed
”
in operation
with two control circuits.
Motorheating
(12D)
Motorheating ON / OFF
Switch over direction
of rotation
(13D)
Reverse direction of rotation
“
right-hand
”
/
“
left-hand
”
(only for frequency inverter with
3 ~ output)
Freeze function
(14D)
“
Freeze function
”
= maintain momentary modulation value
Override Time
(21D)
Overwrite timer function (in operation with timer)
For mode speed controller
1.01
Setpoint1/2
(5D)
Switch over
“
Set Intern1
”
/
“
Set Intern2
”
“
Setting External 1
”
must be at
“
OFF
”
.
Setpoint int./ext.
(6D)
Switch over
“
Intern
”
/
“
Extern
”
For modes as controller from
2.01
Setpoint1/2
(5D)
Switch over
“
Setpoint 1
”
/
“
Setpoint 2
”
for control circuit1
Setpoint int./ext.
(6D)
Switch over
“
Intern
”
/
“
Extern
”
Possible only for operation with one control circuit!
Control/Manual
(7D)
Switch over
“
automatic control
”
/
“
Speed manual
”
Possible only for operation with one control circuit!
Heating/Cooling
(8D)
Switch over control function (e.g.
“
heating
”
/
“
cooling
”
)
1.Setp+Pband1/2
(15D)
for control circuit 1: Switch over Setpoint 1/2 and Pband 1/1
When programming this function,
“
Setting
”
additionally lists the parameter:
“
1.Pband2
for control circuit 1.
”
Only active in operation with a second control circuit!
2. Setpoint 1/2
(9D)
for control circuit 2: Switch over
“
Setpoint 1
”
/
“
Setpoint 2
”
2.Setp+Pband1/2
(16D)
for control circuit 2: Switch over Setpoint 1/2 and Pband 1/2
When programming this function,
“
Setting
”
additionally lists the parameter:
“
2Pband2
for control circuit 2.
”
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Menu tables
L-BAL-E212-GB 1451 Index 003
Part.-No.
109/123