Input PIN
|
0010
|
to exit the protected area
→
→
→
→
→
50.0 Hz
Setting direct
Back
- - - - -
PIN input
Enter
0010
PIN input
Enter
Start
Setting
Protocol
Base setup
Controller Setup
IO Setup
5
Setting Step
adjust PIN 0010
9.2
Temperature control
2.01
...
2.05
9.2.1
Basic setting
2.01
...
2.05
Main menu
Base setup
Setting
Protocol
Base setup
Controller Setup
IO Setup
Base setup
Mode
Mode selection e.g.
2.01
2.01
Mode
Base setup
E1 Analog In
The sensor input is factory set in modes of group
2
to sensors of the
“
TF
”
type series
(sensor type KTY81-210).
Measuring range: -50.0...+150
°
C
Connection terminals:
“
GW E1 Viive
”
and
“
T
”
Other settable sensors:
•
PT1000
at terminals
“
E1
”
and
“
T
”
, (measuring range -50.0...+150
°
C)
•
MTG-120V (type designation for active sensor with 0 - 10 V output, connection to
terminals
“
E1
”
,
“
GND
”
and
“
24 V
”
, measuring range: -10...+120
°
C)
•
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
order to display the actual value correctly.
Example with a 0 - 10 V sensor and 0 - 100
°
C measurement range:
E1 Analog In = 0 - 10 V, E1 Unit =
°
C, E1 Decimals = 1, E1 Min. = 0,0
°
C, E1 Max. =
100,0
°
C,
When selecting sensors with active signal, the setpoint and the Pband are automati-
cally set to the 1/2 measuring range.
TF
E1 Analog In
Base setup
E1 Offset
Sensor calibration with calibrated comparison device.
The current
“
E1 Actual
”
is displayed including the offset set here.
20.0
°
C
E1 Offset
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.