8

GB

Installation Instructions

Inspection

Upon reception, inspect the equipment and
notify both the carrier and the insurance
company, in writing, of any possible dam-
age.

Environmental protection

Eliminate packing in accordance
with the regulations in force on en-
vironmental conservation.
During installation and mainte-

nance, keep in mind that HFC-410A and oil
POE are used.

Safety

Installation and maintenance operations of
this air conditioning system should be car-
ried out only by qualified and expert per-
sonnel. Periodical maintenance operations
should be carried out, such as cleaning the
coils and air filters, so as to keep unit per-
formance at an optimum.

Caution

This unit should be installed and
used in accordance with:

- Low Voltage Electrotechnical Regulations.
- Safety Regulations for Cooling Plants and

Installations.

- Regulations on Pressure Equipment.
- Basic Construction Standards.
- Technical Construction Standards.
- Local ordinances.

Location

 (Fig. 1 to 3)

To be installed directly outdoors. Place the
unit on a consistent base and fasten by
means of bolts.

Outdoor units

These units are supplied with an adequate
R-410A refrigerant load for an interconnect-
ing tubing length of 5 meters.
Each unit includes a connecting elbow for
the condensed water drain (on heat pump
models only). Each compressor is equipped
with an acoustic isolation casing to reduce
noise to a minimum.

Installation

Unit installation comprises:

- Unit mounting.
- Refrigerant tubing connections.
- Condensed water drain connections in

heat pump units.

- Unit wiring.

Clearances, outdoor unit

A minimum clearance is required around the
units for the circulation of air and access for
maintenance servicing, as indicated in the
general dimensions.

Interconnection of the units

When installing Split units, the cooling cir-

cuit should be completely leakproof after
mounting.
This will help to obtain maximum perform-
ance with minimum consumption, and avoid
serious damage to the unit. This is an eco-
logical precaution as well.

Installation of interconnecting
tubing

The length of the interconnecting tubing of
the units should be as short as possible. The
maximum admissible distances with regard
to the circuit and standard tubing diameters
are indicated on each apparatus of the cor-
responding indoor units.

Tubing to be used

Special care should be taken that the tub-
ing that interconnects the two units is kept
clean and dry, even prior to installation. It is
advisable to take into account the following
recommendations:
- Use copper refrigerant quality tubing only.
- Do not work outdoors when raining.
- The ends of the tubing should remain

closed during installation.

- Do not leave dryer filters or the compres-

sor out in the open air.

- For welding use low melting point rods

with a 5% silver content, minimum.

- When welding and as long as the tubing

is hot, maintain a flow of dry nitrogen so
as to avoid internal rusting and scaling
that could cause contamination and ob-
structions.

- Do not use strippers on copper-copper

joints.

- Connection between units should be car-

ried out by means of the flaring method.

Insulation of refrigerant tubing

Due to the fact that the capillary tubing is
installed in the outdoor unit, both the larger
as well as the smaller diameter tubes are in
the relative low pressure side of the system.
Consequently, to avoid condensed water
dripping on the floor, both tubes should be
insulated adequately. The thickness of same
should be at least 8 mm. See Fig. 4.

Emptying and dehydrating
(Fig. 5)

Air does not act as a refrigerant since it can-
not be liquefied by the compressor. Any air
and humidity remaining in the cooling sys-
tem has undesirable effects, as indicated
below. Consequently, they should be elimi-
nated completely.
- High pressure increases.
- Consumed power supply increases.
- Equipment performance decreases.
- Water contained in the air could freeze

and block the capillaries.

- Water can cause corrosion of certain parts

of the circuit, and deterioration of the com-
pressor.

Process

- Fit an adapter to the pump to avoid con-

tamination of the POE oil.

- Connect the vacuum pump and service

pressure gauges to the system.

- Carry out a vacuum of up to at least 50

microns.

- Make sure the system does not loose

vacuum.

- If it does, detect leaks and repair.

Cooling Interconnections

R-410A refrigerante
- R-410A refrigerant is a 50% binary mix-

ture of HFC-32 and HFC-125. Its reaction
as a refrigerant gas is nearly azeotropic
(creep below 0.17°K). Does not contain
chlorine and, thus, it does not harm the
ozone layer. Nevertheless, should a cir-
cuit be drained, the gas should always be
recovered and in no case released in the
atmosphere.

- In comparison to R-22, R-410A operates

at higher pressures. At 60% higher on the
high side and at 75% more on the low
side. See following table.

- R-410A refrigerant should be charged al-

ways in liquid form. Should the tank not
have a dipping pipe, it should be turned
upside down.

- The R-410A refrigerant tanks stand out

because they are pink.

- Due to the fact that it does not contain

chlorine, R-410A refrigerant can be used
only in combination with POE (Polyol Es-
ter) type synthetic oil.

- R-410A refrigerant is not flammable at at-

mospheric pressure. Nevertheless, as it
contains 50% HFC-32, it should never be
pressurised with air or any gas other than
nitrogen (the same as R-22).

POE oil
- POE oil is highly hygroscopic. Its water

absorbing capacity is 15 times greater
than mineral oil.

- POE oil containers should be metallic and

should be kept open the least time possi-
ble. They should be hermetically sealed
after use.

- Never open a circuit or compressor

charged with POE oil while under vacuum.
Should either one be under atmospheric
pressure, it should not remain open for
more than 15 minutes. Should this not be
possible, a flow of dry nitrogen should be
established.

- POE oil cannot be mixed with mineral oil.

Amounts of over 5% of mineral oil mixed
with POE will cause transitory obstruc-
tions within the expansion systems.

54

20.3

32.6

43

15.2

25

7

5.2

8.9

Temperature

  °C

R-22 pressure

bar g

R-410A

pressure bar g

-1

3.8

6.8

Summary of Contents for YVJC09DS-AAA

Page 1: ...stallation 11 13 P Condensadoras de bomba de calor com tecnologia Inverter Instru es de Instala o 14 16 I Unit esterna pompa di calore con tecnologia Inverter Istruzioni per l installazione 17 19 D Ve...

Page 2: ...2...

Page 3: ...rvice analysator Serviceanalysator 1 Unidad interior Indoor unit Unit int rieure Unidade interior Unit interna Innenger t Binnenunit Innvendig enhet 2 Unidad exterior Outdoor unit Unit ext rieure Unid...

Page 4: ...enerales General dimensions Dimensions g n rales Dimens es gerais Dimensioni d ingombro Allgemeine Abmessungen Algemene afmetingen Generelle dimensjoner YVJC09DS AAA YVJC12DS AAA 150 2000 500 300 848...

Page 5: ...bre de calidad fri gor fica No efectuar trabajos en el exterior si est lloviendo Los extremos de los tubos deben perma necer cerrados mientras dure la instala ci n No dejar abiertos al ambiente los fi...

Page 6: ...presen cia excesiva de humedad provocar la aparici n de lodos y cidos que da ar n el compresor Por ello el aceite contami nado debe ser substituido o recuperado mediante filtros Debido a su alta higr...

Page 7: ...interior 27 C TS 19 C TH Temperatura aire exterior 35 C TS tuber as 4 metros La capacidad calor fica nominal se basa en Temp aire interior 21 C TS Temperatura aire exterior 7 C TS 6 C TH tuber as 4 me...

Page 8: ...e contamination and ob structions Do not use strippers on copper copper joints Connection between units should be car ried out by means of the flaring method Insulation of refrigerant tubing Due to th...

Page 9: ...pump from flowing towards the circuit charged with POE oil With adapter for UNF 20 thread Electronic scale Needed because it is im possible to charge R 410A by using a charge cylinder due to the bubbl...

Page 10: ...t YVJC09DS AAA YVJC12DS AAA Capacities Nominal in Cool W 2 500 3 500 Inverter variations in Cool W 1 000 3 200 1 400 3 500 Nominal in Heat W 2 700 3 800 Inverter variations in Heat W 1 100 4 000 1 500...

Page 11: ...es tubes doivent tre tou jours bouch s tant que dure l installation Ne pas laisser les filtres d shydrateurs ni le compresseur expos s l air libre Pour souder utiliser des baguettes bas point de fusio...

Page 12: ...rouge l chelle de 1 53 bar Celui de basse pression couleur bleu l chelle de 1 38 bar Raccords viss s UNF 20 Tuyaux En caoutchouc HNBR et fourreau int rieur en nylon Pression de travail 5 1 Mpa pressio...

Page 13: ...des autres compo sants doit tre effectu par un installateur comp tent conform ment la l gislation en vigueur Contacter les autorit s locales pour obtenir plus d information ATTENTION Unit ext rieure...

Page 14: ...e conta as orienta es que se oferecem nas seguintes reco menda es Utilizar somente tubo de cobre de quali dade frigor fica N o efectuar trabalhos no exterior se es tiver a chover As extremidades dos t...

Page 15: ...lta de cor vermelha com a esca la de 1 a 53 bar O de baixa de cor azul com a escala de 1 a 38 bar Os dois providos de liga es com rosca de 1 2 UNF 20 Mangueiras De borracha HNBR e com forro interior d...

Page 16: ...mento do refrigerante do leo e doutros compo nentes deve ser efectuado por um instalador qualificado de acordo com a legisla o aplic vel Contacte as autoridades locais para obter mais informa o ATEN O...

Page 17: ...o due minuti i filtri deidratatori o il com pressore Per saldare utilizzare elettrodi a basso punto di fusione e con un contenuto d ar gento di almeno il 5 Durante la saldatura e finch il tubo sia ca...

Page 18: ...e diante filtri Data la sua elevata igroscopicit l olio POE pu occasionare ustioni cutanee Si consiglia l impiego di guanti quando lo si maneggia Gli oli POE adeguati per sistemi con R 410A sono i seg...

Page 19: ...nenti deve essere effettuato da un installatore competente come prescritto dalla legislazione applicabile Per maggiori informazioni rivolgersi alle autorit locali ATTENZIONE Unit esterna YVJC09DS AAA...

Page 20: ...ist darauf zu achten dass die verwendeten Rohre be reits vor ihrem Einsatz durchweg sauber und trocken sind Im weiteren sollten dann die folgenden Empfehlungen beachtet werden Nur k ltetechnisches Kup...

Page 21: ...m men die folgenden Polyolester le in Fra ge MOBIL EAL ARCTIC 22 CC ICI EMKARATE RL32CF ICI Spezifisches Werkzeug Zur Aufstellung von mit K ltemittel R 410A und Polyolester l arbeitendenAnlagen sind d...

Page 22: ...en Komponenten obliegt dem gesetzlich zust ndigen Installateur Weitere Auskunft erhalten Sie bei den zust ndigen Beh rden vor Ort ACHTUNG Au enger t YVJC09DS AAA YVJC12DS AAA Leistungswerte Nennleistu...

Page 23: ...ening te houden met de onderstaande aanwijzingen Uitsluitend koperbuis gebruiken van een kwaliteit die geschikt is voor koelleidingen Geen werkzaamheden buiten uitvoeren wanneer het regent De uiteinde...

Page 24: ...ijderen Een teveel aan vocht veroorzaakt slib en zu ren die de compressor beschadigen Daarom dient de verontreinigde olie ver vangen of middels filter opgevangen te worden Als gevolg van de hoge mate...

Page 25: ...middel olie en andere onderde len dient door een bevoegd installateur overeenkomstig de van toepassing zijnde wetgeving uitgevoerd te worden Voor nadere informatie kunt u contact met de plaatselijke o...

Page 26: ...og spon inne i r ret som kunne for rsake forurensning og blokkeringer Ved koblinger av to kobberr r m man ikke bruke etsende midler Koblingen til enhetene m gj res ved hjelp av utvidelsesmetoden Isol...

Page 27: ...noe av mineraloljen i pumpen skal renne mot kretsen fylt med POE olje Med tilpasser for UNF 20 skruegjenge Elektronisk vekt Denne er n dvendig fordi det ikke er mulig fylle R 410A ved hjelp av en fyl...

Page 28: ...retas av en kvalifisert installat r i samsvar med gjeldende lovgivning Ta kontakt med lokale myndigheter hvis du nsker mer informasjon OBS Utvendig enhet YVJC09DS AAA YVJC12DS AAA Kapasitet Nominell p...

Page 29: ...29...

Page 30: ...30...

Page 31: ...9 392 EEC 89 336 EEC NORMAS INTERNACIONALES Y ESPECIFICACIONES T CNICAS APLICADAS Paseo Espronceda 278 08204 SABADELL TYPE EC STANDARDS APPLIED DECLARATION OF COMPLIANCE ON MACHINERY MANUFACTURER CLIM...

Page 32: ...www johnsoncontrols com...

Reviews: