SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
93
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
5
ONE INCH DEFLECTION SPRING ISOLATOR SPECIFICATIONS
NOTES:
1. Use either all CP's or all CP2's at all locations on a unit.
2. Installation requires bolting or anchoring mount to support structure with a 2 x 0.625" diameter bolts or 2 x 0.5" diameter concrete anchors.
3. All springs are designed for 50% over-travel.
CPX-xx-xxx
MODEL NUMBER
COLOR CODE
RATED CAPACITY (FOR UNITS WITH ALL LOAD POINTS
LESS THAN 1785 LBS (810 KG)
(LBS.)
(KG)
PART NUMBER
CP-1D-510
BLACK
Up thru 434
Up thru 197
029-25334-002
CP-1D-900
DARK GREEN
435 thru 765
198 thru 347
029-25334-003
CP-1D-1200
GRAY
766 thru 1020
348 thru 463
029-25334-004
CP-1D-1360
WHITE
1021 thru 1156
464 thru 524
029-25334-005
CP-1D-1785N
GRAY/RED
1157 thru 1785
525 thru 810
029-25334-006
MODEL NUMBER
COLOR CODE
RATED CAPACITY (FOR UNITS WITH ANY LOAD POINT
ABOVE 1518 LBS (689 KG)
(LBS.)
(KG)
PART NUMBER
C2P-1D-1350
DARK PURPLE
Up thru 1148
Up to 521
029-25334-008
C2P-1D-1800
DARK GREEN
1149 thru 1530
522 - 694
029-25334-009
C2P-1D-2400
GRAY
1531 thru 2040
695 - 925
029-25334-010
C2P-1D-2720
WHITE
2041 thru 2312
926 - 1049
029-25334-012
C2P-1D-3570N
GRAY/RED
2313 thru 3570
1050 - 1619
029-25334-013
MOUNT
TYPE
DIMENSION DATA (INCHES)
W
D
L
B
C
T
H
CP
3
5/8
7-3/4
6-1/2
4-3/4
1/2
5-5/8
C2P
3
5/8
10-1/2
9-1/4
7-3/4
9/16
6
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...