SECTION 4 - INSTALLATION
JOHNSON CONTROLS
61
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
4
TABLE 4
- ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS
TERMINAL BLOCK
TERMINAL BLOCK
WITH INDEPENDENT
SYSTEM CIRCUIT
BREAKERS
TERMINAL BLOCK WITH
INDEPENDENT SYSTEM
NON-FUSED DISCONNECT
SWITCHES
SINGLE POINT WIRING
YVAA MODEL
INPUT
VOLTS
INPUT
FREQ
WIRES
PER
PHASE
LUG WIRE
RANGE
WIRES
PER
PHASE
LUG WIRE
RANGE
WIRES PER
PHASE
LUG WIRE
RANGE
FRAME
COND
EV
AP
Models
0368 to 0523
200
60
230
60
380
60
4
#1 - 750 kcmil
4
#1 - 750 kcmil
4
#1 - 750 kcmil
400
50
4
#1 - 750 kcmil
4
#1 - 750 kcmil
4
#1 - 750 kcmil
460
60
4
#1 - 750 kcmil
4
#1 - 750 kcmil
4
#1 - 750 kcmil
575
60
4
#1 - 750 kcmil
4
#1 - 750 kcmil
4
#1 - 750 kcmil
FIELD WIRING LUGS
HIGH AIRFLOW/HIGH STATIC CONDENSER FANS
TERMINAL
BLOCK
CIRCUIT
BREAKER
NON-FUSED
DISCONNECT SWITCH
YVAA MODEL
INPUT
VOLTS
INPUT
FREQ
WIRE
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
FRAME COND EVAP
DUAL POINT WIRING
048
3
G
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
49
0
K
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
050
0
J
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
052
3
J
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...