SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
77
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
5
ALL DIMENSIONS - INCHES (MM)
YVAA
A
B
C
D
E- NOZZLE
SIZE
F
G
WATER
VOLUME
GALLONS
(LITERS)
MINIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER
FLOW
RATE GPM
(L/S)
FRAME
COND.
39
8
16.3
(414)
14
(356)
252.5
(6414)
–
8
83.5
(2121)
–
147
(556)
550 (35)
2160 (136)
41
3
15.5
(394)
14
(356)
164.6
(4181)
–
8
83.8
(2129)
–
130
(492)
470 (30)
1870 (118)
42
5
15.5
(394)
14
(356)
252.6
(6416)
–
8
83.8
(2129)
–
130
(492)
470 (30)
1870 (118)
42
8
16.3
(414)
14
(356)
296.5
(7531)
–
8
83.5
(2121)
–
147
(556)
550 (35)
2160 (136)
44
3
15.8
(401)
13
(330)
287.1
(7292)
282.5
(7177)
8
94.2
(2393)
89.7
(2278)
96
(363)
420 (26)
1660 (105)
47
5
16.3
(414)
14
(356)
308.4
(7833)
–
8
71.5
(1816)
–
147
(556)
550 (35)
2160 (136)
48
3
15.8
(401)
13
(330)
331.2
(8412)
326.6
(8296)
8
94.2
(2393)
89.7
(2278)
96
(363)
420 (26)
1660 (105)
49
0
15.5
(394)
14
(355)
176.5
(4482)
–
8
71.7
(1820)
–
130
(492)
470 (30)
1870 (118)
50
0
16.3
(414)
14
(356)
176.2
(4475)
–
8
71.5
(1816)
–
147
(556)
550 (35)
2160 (136)
52
3
16.3
(414)
14
(356)
308.4
(7833)
–
8
71.5
(1816)
–
147
(556)
550 (35)
2160 (136)
TABLE 8 -
STANDARD TWO-PASS, REAR INLET/OUTLET EVAPORATOR (CONT'D)
NOTE
: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Please contact your Johnson Controls Sales Office for ratings and further information.
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...