SECTION 8 - MICROPANEL
JOHNSON CONTROLS
159
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
8
CONDENSER FANS ON
0
CONDENSER FAN SPEED
XXX % (vsd)
COMPRESSOR HEATER
ON
VI STEP SOLENOID 1
OFF
VI STEP SOLENOID 2
OFF
RUN PERMISSIVE
ON
VSD RUN RELAY
OFF
VSD SOFTWARE RUN SIGNAL
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
RUN TIME
0-0-15-26 D-H-M-S
MOTOR CURRENT
104 AMPS 87 %FLA
SUCTION PRESSURE
57 PSIG
DISCHARGE PRESSURE
233 PSIG
OIL PRESSURE
218 PSIG
CONDENSER LIQUID TEMP
42.9 DEGF
DISCHARGE TEMPERATURE
145.5 DEGF
OIL
TEMPERATURE
102.8
DEGF
SAT CONDENSER TEMP
31.7 DEGF
SUBCOOLING
11.2
DEGF
SAT DISCHARGE TEMP
112.1 DEGF
DISCHARGE SUPERHEAT
33.4 DEGF
MOTOR TMP
XXX.X XXX.X XXX.X DEGF
COMPRESSOR SPEED
XXX.X%
FLASH TANK LEVEL
< 512 ADC
COND DRAIN % OPEN
XXX.X%
ECONOMIZER % OPEN
XXX.X%
CONDENSER FANS ON
3
CONDENSER FAN SPEED
XXX% (vsd)
COMPRESSOR HEATER
OFF
VI STEP SOLENOID 1
OFF
VI STEP SOLENOID 2
OFF
RUN PERMISSIVE
ON
VSD RUN RELAY
OFF
VSD SOFTWARE RUN SIGNAL
OFF
UNIT OPERATING SCHEDULE
S M T W T F S
*=HOLIDAY
MON START=00:00AM
STOP=00:00AM
TUE START=00:00AM
STOP=00:00AM
WED START=00:00AM
STOP=00:00AM
THU START=00:00AM
STOP=00:00AM
FRI START=00:00AM
STOP=00:00AM
SAT START=00:00AM
STOP=00:00AM
HOL START=00:00AM
STOP=00:00AM
SOUND LIMIT SCHEDULE
(if enabled)
MON START=00:00AM
STOP=00:00AM
TUE START=00:00AM
STOP=00:00AM
WED START=00:00AM
STOP=00:00AM
THU START=00:00AM
STOP=00:00AM
FRI START=00:00AM
STOP=00:00AM
SAT START=00:00AM
STOP=00:00AM
HOL START=00:00AM
STOP=00:00AM
History Data Printout
History printouts, when selected, provide stored data
relating to all specific system and chiller operating
conditions at the time of the fault, regardless of wheth-
er a lockout occurred. History information is stored in
battery-backed memory on the Chiller Control Board
and is not affected by power failures or resetting of
faults. Whenever a fault of any type occurs, all system
operating data is stored in battery-backed memory at
the instant of the fault. The history printout is similar
to the operating data printout except for the change in
the header information shown below:
YORK INTERNATIONAL CORPORATION
YVAA SCREW CHILLER
HISTORY NUMBER 1
2:04:14 PM 30 APR 11
SYS 1 YYYYYYY
HIGH DSCH PRESS SHUTDOWN
STATUS AT TIME OF SHUTDOWN
SYS 1 XXXXXXXXXXXXXXXXXXXXXXXXXX
SYS 2 XXXXXXXXXXXXXXXXXXXXXXXXXX
ALL FAULTS
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
The most recent fault will always be stored as
HISTORY BUFFER #1.
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...