JOHNSON CONTROLS
124
SECTION 7 - OPERATION
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
TABLE 19 -
DISCHARGE PRESSURE LOAD
LIMITING/UNLOADING
DISCHARGE PRESSURE
UN-LOADING
Discharge Pressure Cutout- 20
PSIG and Discharge Pres-
sure Cutout- 15 PSIG
0 Hz
Discharge Pressure Cutout- 13.5 PSIG
1 Hz
Discharge Pressure Cutout- 12 PSIG
2 Hz
Discharge Pressure Cutout- 10.5 PSIG
3 Hz
Discharge Pressure Cutout- 9 PSIG
4 Hz
Discharge Pressure Cutout- 7.5 PSIG
5 Hz
Discharge Pressure Cutout- 6 PSIG
6 Hz
Discharge Pressure Cutout- 4.5 PSIG
7 Hz
Discharge Pressure Cutout- 3 PSIG
8 Hz
Discharge Pressure Cutout- 1.5 PSIG
9 Hz
Discharge Pressure Cutout- 0 PSIG
10 Hz
Suction Pressure Load Limiting/Unloading
Suction pressure load limiting helps to protect the
evaporator from freezing. A system is permitted to load
normally as long as the Suction Pressure is above the
Suction Pressure Cutout plus 2 PSIG. Between Cut-
out plus 2 PSIG and the Cutout, loading is inhibited,
even though increased loading is required. Between the
Suction pressure Cutout and Suction Pressure Cutout
minus 10 PSIG, forced unloading is performed every 2
seconds according to
. This situ-
ation would occur if the suction pressure cutout tran-
sient override control is in effect (Refer to
Pressure Cutout (Software) Fault on Page 122
suction pressure cutout is programmed under the PRO-
GRAM key. The default Suction Pressure Cutout is set
at 24.0 PSIG.
Suction pressure load limiting is active at startup, to
only prevent loading of the compressors. Suction pres-
sure limit unloading will not occur until the system run
time reaches 5 minutes of operation to allow the sys-
tem to stabilize.
TABLE 20 -
SUCTION PRESSURE LOAD LIMITING/
UNLOADING
SUCTION PRESSURE
UN-LOADING
Suction Pressure is between
2 PSIG and Suc-
tion Pressure Cutout
0 Hz
Suction Pressure Cutout- 1 PSIG
1 Hz
Suction Pressure Cutout- 2 PSIG
2 Hz
Suction Pressure Cutout- 3 PSIG
3 Hz
Suction Pressure Cutout- 4 PSIG
4 Hz
Suction Pressure Cutout- 5 PSIG
5 Hz
Suction Pressure Cutout- 6 PSIG
6 Hz
Suction Pressure Cutout- 7 PSIG
7 Hz
Suction Pressure Cutout- 8 PSIG
8 Hz
Suction Pressure Cutout- 9 PSIG
9 Hz
Suction Pressure Cutout- 10 PSIG
10 Hz
Sensor Failure Cutout Fault
The Sensor Failure Cutout prevents the system from
running when a critical sensor (transducer, level sen-
sor, or motor winding temp sensor) is not function-
ing properly and reading out of range. This safety is
checked at startup and will prevent the system from
running if one of the sensors has failed.
The sensor failure safety will also fault and shutdown
a system while in operation, if a safety threshold is ex-
ceeded or a sensor reads out of range (high or low).
Following is the Status display fault message.
SYS X YYYYYYYY SENSOR FAILURE:
ZZZZZZZZZZZZ
The X indicates the specific system.
YYYYYYYY will either indicate the system
is in a “FAULT” condition and will restart
when the fault clears, or “LOCKOUT”
after 3 faults and will not restart until the
operator clears the fault using the keypad.
ZZZZZZZZZZZ indicates the failed sensor below:
• SUCT PRESS
• OIL PRESS
• DSCH PRESS
• MOTOR TEMP X *
The Unit Setup Mode allows a specific motor tempera-
ture sensor to be ignored, if it fails.
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...