SECTION 8 - MICROPANEL
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
HISTORY KEY
LD10605
HISTORY
KEY
History Key Operation
The HISTORY key provides the user access to many
unit and system operating parameters captured at the
instant a unit or system safety (fault) shutdown occurs.
The history buffer will also capture system data at the
time of normal shutdowns such as cycling shutdowns.
When the HISTORY key is pressed the following
screen is displayed:
HISTORY
CHOOSE HISTORY TYPE
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
The
◄
and
►
(ARROW) keys allow choosing be-
tween NORMAL SHUTDOWNS and FAULT SHUT-
DOWNS. “Fault” shutdowns provide information on
safety shutdowns, while “Normal” shutdowns provide
chiller cycling information on temperature (demand),
cycling, remote, system switch, and so on, shutdowns
that are non-safety related shutdowns. Once the selec-
tion is made, the
(ENTER) key must be pressed to
enter the selection.
Normal Shutdowns History
If the NORMAL SHUTDOWNS History is selected,
the following screen will be displayed:
NORM HIST XX 18-JUN-2004 10:34:58 AM
YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
XX is the normal shutdown number. The display will
provide date and time of the shutdown and the reason
for the cycling shutdown (YYY….).
The operator can view any of the stored 20 single dis-
play normal shutdown history buffers. History buffer
number 1 provides the most recent shutdown informa-
tion and buffer number 20 is the oldest safety shutdown
information saved. The
◄
and
►
(ARROW) keys allow
scrolling between each of the history buffers. The
►
(ARROW) key scrolls to the next normal history shut-
down and the
◄
(ARROW) key scrolls to the previous
normal history shutdown.
The following display will typically be displayed on a
normal shutdown due to shutdown on lack of cooling
demand.
NORM HIST XX 18-JUN-2004 10:34:58 AM
SYS X COOLING DEMAND SHUTDOWN
Fault Shutdowns History
If the FAULT SHUTDOWNS History is selected, the
following screen will be displayed:
FAULT HIST XX 18-JUN-2004 10:34:58 AM
YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
XX is the FAULT HISTORY shutdown number. The
display will provide the date, time, and a description of
the specific type of fault that occurred (YYY….).
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...