C
D
E-NOZZLE
SIZE
WATER
VOLUME
GALLONS
(LITERS)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
FRAME
COND.
30
5
15.3
(389)
26.7
(678)
166.9
(4239)
70
(1778)
6
71
(269)
200 (13)
780 (49)
30
8
15
(381)
30.3
(770)
132.2
(3358)
71.8
(1824)
6
113
(428)
270 (17)
1060 (67)
31
8
15
(381)
29.5
(749)
176.6
(4486)
71.8
(1824)
6
113
(428)
270 (17)
1060 (67)
32
3
15.5
(394)
29.5
(749)
88.6
(2250)
71.8
(1824)
6
113
(428)
270 (17)
1060 (67)
33
3
15.3
(389)
26.7
(678)
166.9
(4239)
70
(1778)
6
71
(269)
200 (13)
780 (49)
34
3
15.5
(394)
29.5
(749)
132.6
(3368)
71.8
(1824)
6
113
(428)
270 (17)
1060 (67)
34
5
15.5
(394)
29.5
(749)
176.2
(4475)
71.8
(1824)
6
113
(428)
270 (17)
1060 (67)
36
8
16.3
(414)
30.3
(770)
208.6
(5298)
83.5
(2121)
8
147
(556)
370 (23)
1440 (91)
37
3
15.8
(401)
28.8
(732)
180.9
(4595)
112.2
(2850)
6
94
(356)
280 (18)
1100 (69)
37
5
16.3
(414)
30.3
(770)
164.3
(4173)
83.4
(2118)
8
147
(556)
370 (23)
1440 (91)
TABLE 9 -
OPTIONAL THREE-PASS REAR INLET/FRONT OUTLET EVAPORATOR (CONT'D)
NOTE
: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Please contact your Johnson Controls Sales Office for ratings and further information.
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...