JOHNSON CONTROLS
52
SECTION 4 - INSTALLATION
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
TABLE 4 -
ELECTRICAL LUG DATA
FIELD WIRING LUGS
STANDARD & ULTRA QUIET CONDENSER FANS
TERMINAL
BLOCK
CIRCUIT
BREAKER
NON-FUSED
DISCONNECT SWITCH
YVAA MODEL
INPUT
VOLTS
INPUT
FREQ
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
FRAME COND EVAP
SINGLE POINT WIRING
015
3
B
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
4
4/0 ~ 500 kcmil
380
60
2
#2 - 600 kcmil
2
#2/0 ~ 500 kcmil
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
2
#2/0 ~ 500 kcmil
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 ~ 600 kcmil
016
5
B
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
4
4/0 ~ 500 kcmil
380
60
2
#2 - 600 kcmil
2
#2/0 ~ 500 kcmil
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
2
#2/0 ~ 500 kcmil
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 ~ 600 kcmil
017
8
C
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
4
4/0 ~ 500 kcmil
380
60
2
#2 - 600 kcmil
2
#2/0 ~ 500 kcmil
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
2
#2/0 ~ 500 kcmil
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 ~ 600 kcmil
018
3
A
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
4
4/0 ~ 500 kcmil
380
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
400
50
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 ~ 600 kcmil
019
5
A
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
4
4/0 ~ 500 kcmil
380
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
400
50
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 ~ 600 kcmil
019
8
B
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
4
4/0 ~ 500 kcmil
380
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
400
50
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 ~ 600 kcmil
020
0
C
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
4
4/0 ~ 500 kcmil
380
60
3
#2 - 600 kcmil
3
3/0 ~ 400 kcmil
3
#2 ~ 600 kcmil
400
50
3
#2 - 600 kcmil
3
3/0 ~ 400 kcmil
3
#2 ~ 600 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 ~ 600 kcmil
021
3
A
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
4
4/0 ~ 500 kcmil
380
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
400
50
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 ~ 600 kcmil
021
5
C
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
4
4/0 ~ 500 kcmil
380
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
400
50
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
3
#2 ~ 600 kcmil
460
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#2 ~ 600 kcmil
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...