SECTION 4 - INSTALLATION
JOHNSON CONTROLS
59
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
4
FIELD WIRING LUGS
HIGH AIRFLOW/HIGH STATIC CONDENSER FANS
TERMINAL
BLOCK
CIRCUIT
BREAKER
NON-FUSED
DISCONNECT SWITCH
YVAA MODEL
INPUT
VOLTS
INPUT
FREQ
WIRE
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
FRAME COND EVAP
DUAL POINT WIRING
036
8
J
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
037
3
F
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
037
5
J
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
039
8
J
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
041
3
H
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
042
5
H
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
042
8
J
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
044
3
G
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
047
5
J
200
60
230
60
380
60
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
400
50
3
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
460
60
2
#2 - 600 kcmil
3
#3/0 ~ 400 kcmil
3
#3/0 ~ 400 kcmil
575
60
2
#2 - 600 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
TABLE 4
- ELECTRICAL LUG DATA (CONT'D)
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...