JOHNSON CONTROLS
150
SECTION 8 - MICROPANEL
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
OPTIONS KEY
LD10605
OPTIONS
KEY
Options Key Operation
The OPTIONS key provides the user with a display of
unit configuration and the capability to modify the con-
figuration. These options can only be viewed under the
OPTIONS key. To view the current options settings,
press the OPTIONS key. Each press of the OPTIONS
key or press of the ▲ or ▼ (
ARROW) keys will scroll
to the next option setting. The ◄ and ► (
ARROW)
keys allow changing the option choices. The
(EN-
TER) key must be pressed after a selection is made to
save the change in memory.
An explanation of each option message is provided
below.
Display Language Selection
The display language can be selected for English, Ital-
ian, Polish, Hungarian, German, French, Portuguese,
and Spanish.
OPTIONS
DISPLAY LANGUAGE
◄ ►
XXXXXXXXXXXXXXXXXX
The default language will be English.
Chilled Liquid Cooling Mode Selection
The Chilled liquid cooling mode can be selected for
Water Cooling or low temperature Glycol Cooling.
OPTIONS
CHILLED LIQUID COOLING MODE
◄ ►
XXXXXXXXXXXXXXXXXX
When Water Cooling is chosen, the chilled liquid tem-
perature setpoint can only be programmed from 4°C to
21°C (40°F to 70°F).
OPTIONS
CHILLED LIQUID COOLING MODE
◄ ►
WATER COOLING
When Glycol Cooling is chosen, the chilled liquid
temperature setpoint can be programmed from -12°C
to 21°C (10°F to 70°F).
OPTIONS
CHILLED LIQUID COOLING MODE
◄ ►
GLYCOL COOLING
The default Chilled Liquid Mode will be WATER
COOLING.
Local / Remote Control Mode Selection
Local or Remote Control Mode allows the user to se-
lect the chilled liquid temperature control mode.
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...