JOHNSON CONTROLS
158
SECTION 8 - MICROPANEL
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
A sample of the is shown below. The operating data
printout is a snapshot of current system operating con-
ditions when the printout was selected. The sample
shows combined printouts of 2, 3, and 4 circuit units.
The actual printout will only show data for the appro-
priate chiller type.
Bold italic text below a line of print is not
on the actual printout. Bold italic text
indicates information that may not be
available on all printouts or is additional
information to help explain the difference
in a 2/3 or 4 circuit printout.
Operating Data Printout
YORK INTERNATIONAL CORPORATION
YVAA SCREW CHILLER
OPERATING DATA
2:04:14 PM 30 DEC 11
SYS 1
NOT RUNNING
SYS 2
COMPRESSOR RUNNING
OPTIONS
CHILLED LIQUID
WATER
LOCAL/REMOTE MODE
REMOTE
LEAD/LAG CONTROL
AUTOMATIC
REMOTE TEMP RESET
DISABLED
REMOTE CURRENT LIMIT
0 TO 10 V
REMOTE SOUND LIMIT
4 TO 20 MA
(if Sound Limiting enabled)
LOW AMBIENT CUTOUT
ENABLED
PROGRAM VALUES
SUCT PRESS CUTOUT
44 PSIG
LOW AMBIENT CUTOUT
25.0 DEGF
LEAVING LIQUID CUTOUT
36.0 DEGF
MOTOR CURRENT LIMIT
100 %FLA
PULLDOWN CURRENT LIMIT
100 %FLA
PULLDOWN LIMIT TIME
0 MIN
SUBCOOLING SETPOINT
12.0 DEGF
UNIT ID NUMBER
0
SOUND LIMIT SETPOINT
100%
(if Sound Limiting enabled)
UNIT DATA
LEAVING LIQUID TEMP
49.0 DEGF
RETURN LIQUID TEMP
58.2 DEGF
TEMP RATE
XXX.X DEGF/MIN
COOLING RANGE
42.0+/-2.0 DEGF
REMOTE SETPOINT
44.0 DEGF
AMBIENT AIR TEMP
74.8 DEGF
LEAD SYSTEM
SYS 2
FLOW SWITCH
ON
EVAPORATOR PUMP RUN
ON
EVAPORATOR HEATER
OFF
ACTIVE REMOTE CONTROL
NONE
OPERATING HOURS 1=XXXXX,
2=XXXXX
START COUNTER 1=XXXXX,
2=XXXXX
SOFTWARE VERSION
C.ACS.XX.00
VSD DATA
ACTUAL FREQUENCY
XXX.X HZ
COMMAND FREQUENCY
XXX.X HZ
DC BUS VOLTAGE
XXX VDC
INTERNAL AMBIENT TEMP
XXX.X DEGF
COOLING SYSTEM STATUS
XXX
BASEPLATE TEMPS
XXX XXX DEGF
PRECHARGE SIGNAL
XXX
MOTOR OVERLOADS 1/2
XXX XXX AMPS
SOFTWARE VERSION
C.VSD.XX.00
UNIT SERIAL NUMBER
YYYY XXXZZZ
SYSTEM 1 DATA
COMPRESSOR STATUS
OFF
RUN TIME
0- 0- 0- 0 D-H-M-S
MOTOR CURRENT
0AMPS
0 %FLA
SUCTION PRESSURE
125 PSIG
DISCHARGE PRESSURE
131 PSIG
OIL PRESSURE
130 PSIG
CONDENSER LIQUID TEMP
68.4 DEGF
DISCHARGE TEMPERATURE
68.8 DEGF
OIL TEMPERATURE
68.8 DEGF
SAT SUCTION TEMP
71.8 DEGF
SUBCOOLING
3.4 DEGF
SAT DISCHARGE TEMP
74.5 DEGF
DISCHARGE SUPERHEAT
6.3 DEGF
MOTOR TMP
XXX.XXXX.XXXX.XDEGF
COMPRESSOR SPEED
XXX.X %
FLASH TANK LEVEL
> 512 ADC
COND DRAIN % OPEN
XXX.X %
ECONOMIZER % OPEN
XXX.X %
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...