JOHNSON CONTROLS
110
SECTION 7 - OPERATION
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
SC-EQ OR E-LINK BAS COMMUNICATIONS
CARD
Received Data (Control Data)
The chiller receives eight data values from the SC-EQ or
E-Link. The first four are analog values and the last four
are digital values. These eight data values are used as
control parameters when in REMOTE mode. When the
unit is in LOCAL mode, these eight values are ignored.
If the unit receives no valid YorkTalk 2 transmission for
5 minutes it will revert back to all local control values.
lists the control parameters.
Transmitted Data
After receiving a valid transmission from the SC-EQ or
E-Link, the chiller will transmit either operational data
or history buffer data depending on the History Buffer
Request, ENG PAGE 10, found in
. Data must be transmitted for every page. If there
is no value to be sent to a particular page, a zero will be
sent.
shows the data values and
page listings for this unit.
LD22443
1
2
1
2
J16
J1
+12V
TB2
PORT
1
PORT
2A
5
4
3
2
1
GND
SHLD
SHLD
COMM
RS - 485
RS - 485
RS - 485
GND
485+
485-
+5V
-
+
SHLD
COMM
-
+
TB1
5
4
3
2
1
6
A
B
PORT 4
LON E-LINK GATEWAY OPTION
E-LINK GATEWAY
Connection to BACnet, Modbus
or N2 BAS network (See ELINK
Installation Manual
P/N 24-10404-9 for
Installation Requirements.)
031-03478-xxx
Control Board
Connect to Printer
LON FTT10
LON E-Link or SC-EQ interface requires communication
port set for YorkTalk2. See
or settings.
FIGURE 20 -
LON E-LINK GATEWAY OPTION
Summary of Contents for YVAA
Page 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...