SOUND LIMIT CONTROL (CON'T)
(LOCAL AND REMOTE RESET CONTROL)
0 – 10 VDC Reset Input
A 0 VDC signal produces a 0% sound limit (no change
to max VSD freq). A 10 VDC signal produces a 100%
sound limit (max VSD freq = min VSD freq). The
sound limit is ramped linearly between these limits as
the input varies between 0 VDC and 10 VDC. In order
for this input to work properly, the Remote Sound Limit
must be programmed for 0 – 10 VDC input (OPTIONS
key) and Chiller Control Board jumper JP6 placed in
the “V” position.
2 – 10 VDC Reset Input
A 0 - 2 VDC signal produces a 0% sound limit (no
change to max VSD freq). A 10 VDC signal produces
a 100% sound limit (max VSD freq = min VSD freq).
The sound limit reset is ramped linearly between these
limits as the input varies between 2 VDC and 10 VDC.
In order for this input to work properly, the Remote
Sound Limit must be programmed for 2 – 10 VDC input
(OPTIONS key) and Chiller Control Board jumper JP6
placed in the “V” position.
0 – 20 mA Reset Input
A 0 mA signal produces a 0% sound limit (no change
to max VSD freq). A 20 mA signal produces a 100%
sound limit (max VSD freq = min VSD freq). The sound
limit reset is ramped linearly between these limits as
the input varies between 0 mA and 20 mA. In order for
this input to work properly, the Remote Sound Limit
must be programmed for 0 – 20 mA input (OPTIONS
key) and Chiller Control Board jumper JP6 placed in
the “mA” position.
4 – 20 mA Reset Input
A 0 - 4 mA signal produces a 0% sound limit (no change
to max VSD freq). A 20 mA signal produces a100%
sound limit (max VSD freq = min VSD freq). The sound
limit reset is ramped linearly between these limits as
the input varies between 4 mA and 20 mA. In order for
this input to work properly, the Remote Sound Limit
must be programmed for 4 – 20 mA input (OPTIONS
key) and Chiller Control Board jumper JP6 placed in
the “mA” position.
7
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...