4-Compressor Units High Efficiency Dual Point (See Figs. 10 & 11)
(One Field Provided Power Supply Circuit.
Field Connections to Factory provided Terminal Block (Standard), or Individual System Breakers(Optional).
High Efficiency YCAV_ _ _ _ E/V
Model No./
Nameplate
System 1
System 2
System 3
System 4
Control
Compr
Cond.
Fans
Compr
Cond. Fans
Compr Cond. Fans Compr
Cond. Fans Sys
1/3
Sys
2/4
YCAV Volts
(11)
Freq
RLA
(6)
Qty. FLA
(EA)
RLA
(6)
Qty.
FLA
(EA)
RLA
(6)
Qty.
FLA
(EA)
RLA
(6)
Qty.
FLA
(EA)
KVA
(8)
KVA
(8)
0397
380
60
173
5
3.5
173
5
3.5
173
5
3.5
173
5
3.5
2.4
1.8
460
60
137
5
2.8
136
5
2.8
137
5
2.8
136
5
2.8
2.4
1.8
575
60
109
5
2.2
109
5
2.2
109
5
2.2
109
5
2.2
2.4
1.8
0417
380
60
179
6
3.5
179
6
3.5
193
5
3.5
193
5
3.5
2.4
1.8
460
60
141
6
2.8
141
6
2.8
153
5
2.8
152
5
2.8
2.4
1.8
575
60
113
6
2.2
113
6
2.2
122
5
2.2
122
5
2.2
2.4
1.8
0477
380
60
231
6
3.5
231
6
3.5
177
6
3.5
177
6
3.5
2.4
1.8
460
60
182
6
2.8
182
6
2.8
139
6
2.8
139
6
2.8
2.4
1.8
575
60
146
6
2.2
146
6
2.2
112
6
2.2
112
6
2.2
2.4
1.8
High Efficiency YCAV_ _ _ _ E/V
YCAV
Field Wiring Lugs
Field Wiring Lugs
STD Terminal Blocks
OPT Circuit Breakers
Lugs/Phase (1)
Lug Wire Range
Lugs/Phase (1)
Lug Wire Range
Sys 1/3
Sys 2/4
Sys 1/3
Sys 2/4
Sys 1/3
Sys 2/4
Sys 1/3
Sys 2/4
0397
3
3
#2 - 600 KCM
#2 - 600 KCM
3
3
#3/0 - 400 KCM
#3/0 - 400 KCM
2
2
#2 - 600 KCM
#2 - 600 KCM
2
2
#2/0 - 500 KCM
#2/0 - 500 KCM
2
2
#2 - 600 KCM
#2 - 600 KCM
2
2
#2/0 - 500 KCM
#2/0 - 500 KCM
0417
3
3
#2 - 600 KCM
#2 - 600 KCM
3
3
#3/0 - 400 KCM
#3/0 - 400 KCM
2
2
#2 - 600 KCM
#2 - 600 KCM
2
2
#2/0 - 500 KCM
#2/0 - 500 KCM
2
2
#2 - 600 KCM
#2 - 600 KCM
2
2
#2/0 - 500 KCM
#2/0 - 500 KCM
0477
3
3
#2 - 600 KCM
#2 - 600 KCM
3
3
#3/0 - 400 KCM
#3/0 - 400 KCM
2
2
#2 - 600 KCM
#2 - 600 KCM
2
2
#2/0 - 500 KCM
#2/0 - 500 KCM
2
2
#2 - 600 KCM
#2 - 600 KCM
2
2
#2/0 - 500 KCM
#2/0 - 500 KCM
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...