211
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
ACCELERATION/DECELERATION RATE WHEN
STARTING/STOPPING COMPRESSORS
VSD ACCELERATION AND
DECELERATION RATES
The acceleration rate changes with frequency and fol-
lows the guidelines below:
·
Between 0 and 50 Hz, the acceleration is 10 Hz/
sec.
·
Between 50 and 200 Hz, the acceleration is 30.4
Hz/sec. Even though the accel rate of 30.4 Hz/sec
is possible up to 200 Hz, the frequency (speed) is
limited by the minimum start frequency and the
add a compressor frequency calculation performed
by the micro when bringing on an additional
compressor.
When decelerating, the deceleration rate changes with
frequency and follows the guidelines below:
·
Between 200 and 100 Hz, the deceleration time is
30.4 Hz/sec.
·
Between 100 and 0 Hz, the deceleration time is 10
Hz/sec.
When a compressor stops, back-spin of the compressor
will often occur as the pressure differential between
discharge and suction equalizes. This should not be a
cause of concern.
7
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...