12
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
Product Description
PRODUCT DESCRIPTION
INTRODUCTION
YORK YCAV R134a chillers are designed for water
or glycol cooling. All units are designed to be located
outside on the roof of a building or at ground level.
The units are completely assembled with all intercon-
necting refrigerant piping and internal wiring, ready for
field installation.
Prior to delivery, the unit is pressure tested, evacuated,
and fully charged with refrigerant and oil in each of the
two independent refrigerant circuits. After assembly,
an operational test is performed with water flowing
through the cooler to ensure that each refrigerant circuit
operates correctly.
The unit structure is manufactured from heavy gauge,
galvanized steel. Many external structural parts are
coated with “Champagne” baked-on enamel powder
paint. This provides a finish which, when subjected to
ASTM B117, 1000 hour, 5% salt spray conditions, shows
breakdown of less than 1/8” either side of a scribed line
(equivalent to ASTM D1654 rating of “6”).
All exposed power wiring is routed through liquid-tight,
non-metallic conduit.
General System Description
The Latitude (YCAV) Air Cooled Chiller line combines
the best of modern screw compressor design with the
latest technology in variable speed drives. The result is
superior control and efficiency in real world conditions.
The VSD enables slowing the speed of the compressor to
match the load on the system resulting in precise chilled
liquid control, minimized sound, maximum energy ef-
ficiency, and reduced cost of ownership. The VSD also
provides soft starts with no electrical inrush. The lack
of heat build-up on start also enables required off time
between starts to be reduced to a period of 2 minutes.
The YCAV Air-Cooled Screw Chiller utilizes many
components, which are the same or nearly the same as
a standard screw chiller of a similar size. This includes
modular frame rails, condenser, fans, compressors and
evaporator.
The chiller consists of 3 or 4 screw compressors in a
corresponding number of separate refrigerant circuits,
a single shell and tube DX evaporator, an air-cooled
condenser, flash tanks, drain/feed valves, oil separators,
and compressor mufflers. Oil separators utilize no mov
-
ing parts and are rated for a 405 PSIG design working
pressure. Oil cooling is accomplished by routing oil
from the oil separator through several rows of tubes in
the air cooled condenser.
50074d
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...