- 79 -
Model
YDS-71KC15IA
YDS-80KC15IA
YDS-90KC15IA
YDS-112KC15IA
YDS-140KC15IA
Power supply
Ph-V-Hz
1Ph-220-240V-50Hz
Capacity
Capacity
kW
7.1 8 9 11.2 14
Cooling
Input
W
115 115 160 160 180
Capacity
kW
8 9 10
12.5 15
Heating
Input
W
115 115 160 160 180
Motor
Input
W
120/110/100 165/143/114
204
Capacitor
uF
3.5UF/450V 3.5UF/450V
4
Speed (Hi/Me/Lo)
r/min
800/670/550 840/770/640
770/640/550
Coil
Number of rows
2
3
Tube pitch(a)x row pitch(b)
mm
21x13.37
Fin spacing
mm
1.45
1.5
Fin type
Hydrophilic Aluminum
Ф
7
Tube outside dia. and type
mm
Inner groove Tube
Coil length x height x width
mm
1959.4x168x26.74
1916x252x40.1
Number of circuits
8
2
Performance
Noise level (Hi/Me/Lo)
dB(A)
48/45/42 53/48/45
48/45/43
Air flow (Hi/Me/Lo)
m
3
/h
1220/1010/820 1540/1300/1120
1802/1483/1284
Piping size
Liquid / Gas side
mm
Ф
9.53/
Ф
15.9
Containerization
Dimension (WxHxD)
mm
840x230x840 840x300x840
Packing (WxHxD)
mm
955x247x955 955x317x955
Unit
Net/Gross weight
kg
30/34 36/41
Dimension (WxHxD)
mm
950x46x950
Packing (WxHxD)
mm
1035x90x1035
Panel
Net/Gross weight
kg
6/9
Qty per 20’/40’/40’HQ
Pieces
62/132/135
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temp. : 27°CDB, 19°CWB, and outdoor temp.:35°CDB, equivalent
ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.: 7°CDB, 6°CWB, and equivalent ref.
Piping: 8m (horizontal)
Summary of Contents for R-410A
Page 103: ...Wall mount 102 Part 4 2 Wall Mounted...
Page 113: ...Wall mount 112 4 Dimensions 4 1 YDS 22 36EC 4 2 YDS 45 56EC...
Page 115: ...Wall mount 114 5 Piping Diagrams 5 1 YDS 22 56EC 5 2 YDS 22 56HC...
Page 116: ...Wall mount 115 6 Wiring diagrams 6 1 YDS 22 36EC 6 2 YDS 45 56EC...
Page 117: ...Wall mount 116 6 3 YDS 22 56HC...
Page 118: ...Wall mount 117 7 Sound level 7 1 Test condition 7 2 Noise spectrums YDS 22 36EC HC...
Page 119: ...Wall mount 118 YDS 45 56EC HC...
Page 120: ...Wall mount 119 8 Velocity temperature distribution Discharge angle 70...