Controller
___________________________________________________________________________________
- 293 -
2. Check, the check procedure is as follows:
3. CN14
,
Low pressure protection
(
L-PRO
)
, Check with +5vweak electric signal;
4. CN13 High pressure protection H-PRO, Check with +5vweak electric signal;
5. CN12
,
Inter-communication between indoor and outdoor units, RS-485 signal (COM).The
digital pipe will display “E2” malfunction when the indoor and outdoor units can’t communicate
for 1 minute.
6. Current protector, the one–phase current of fixed-speed compressor will pass this current
protector and when the current is more than 16A, it will cut the power supply immediately to
protect the compressor.
7. Current protector, the one–phase current of digital scroll compressor will pass this current
protector and when the current is more than 16A, it will cut the power supply immediately to
protect the compressor.
8. CN11
,
Discharge temperature sensor of digital compressor COM.PIPE
)
, which inside in the
digital compressor, the relevant temperature to sensor please see the appendix 2. If the
discharge temperature is more than 140
O
C, the compressor and all of the system will stop and
restart until the malfunction is eliminated.
9. CN6
,
Three-phase power supply input
,
only check the phase-sequence or loss-sequence
for the first time power on. The digital pipe display “E1” when first power on, the system will
recover until there is no phase-sequence or loss-sequence occur. If there is no phase-sequence
or loss-sequence occur for the first power on, the system will not check the phase-sequence or
loss-sequence until power on over again.
Summary of Contents for R-410A
Page 103: ...Wall mount 102 Part 4 2 Wall Mounted...
Page 113: ...Wall mount 112 4 Dimensions 4 1 YDS 22 36EC 4 2 YDS 45 56EC...
Page 115: ...Wall mount 114 5 Piping Diagrams 5 1 YDS 22 56EC 5 2 YDS 22 56HC...
Page 116: ...Wall mount 115 6 Wiring diagrams 6 1 YDS 22 36EC 6 2 YDS 45 56EC...
Page 117: ...Wall mount 116 6 3 YDS 22 56HC...
Page 118: ...Wall mount 117 7 Sound level 7 1 Test condition 7 2 Noise spectrums YDS 22 36EC HC...
Page 119: ...Wall mount 118 YDS 45 56EC HC...
Page 120: ...Wall mount 119 8 Velocity temperature distribution Discharge angle 70...