Installation
___________________________________________________________________________________
___________________________________________________________________________________
- 254 -
4.5) Precautions:
4.5.1 Refrigerant pipe must use the pipe with specified diameter.
4.5.2 Branch Part should be installed in horizontal mode or vertical mode.
A
B
4.5.2 Y shape three-way pipe should be installed in horizontal mode with ground.
A
B
4.5.4 Horizontal installation of throttling unit (throttling unit is an external unit, so it need
be connected on site)
Caution:
a. Install the throttling part upright, and ensure that it does not incline or is reversed.
b. Use two spanners to connect the electronic throttling part with the pipes of the indoor and
outdoor units, so as to avoid the copper pipe from deforming or getting broken.
c. Use flaring opening to connect the electronic throttling part with the pipes of the indoor and
outdoor units. Do not use welding for the connection, because the heat caused during the
welding process will be transferred to the electronic expansion valve via the copper pipe, which
may damage the electronic expansion valve.
d. Pay attention to the connection direction (refer to the label on the electronic throttling part).
e. For the installation size of the electronic throttling part, see the above figure.
Summary of Contents for R-410A
Page 103: ...Wall mount 102 Part 4 2 Wall Mounted...
Page 113: ...Wall mount 112 4 Dimensions 4 1 YDS 22 36EC 4 2 YDS 45 56EC...
Page 115: ...Wall mount 114 5 Piping Diagrams 5 1 YDS 22 56EC 5 2 YDS 22 56HC...
Page 116: ...Wall mount 115 6 Wiring diagrams 6 1 YDS 22 36EC 6 2 YDS 45 56EC...
Page 117: ...Wall mount 116 6 3 YDS 22 56HC...
Page 118: ...Wall mount 117 7 Sound level 7 1 Test condition 7 2 Noise spectrums YDS 22 36EC HC...
Page 119: ...Wall mount 118 YDS 45 56EC HC...
Page 120: ...Wall mount 119 8 Velocity temperature distribution Discharge angle 70...