Installation
___________________________________________________________________________________
___________________________________________________________________________________
- 275 -
The following table takes steel pipeline as an example, the other thickness of the pipeline
material can be looked up in the correlative standard of the book <construction and accept
criterion>
Square pipeline 600/630
Type Pipeline
Diameter
(long border )
dimension
Ground
pipeline
Middle and low
pressure system
High pressure system
80—320 0.5 0.5
340—450 0.6 0.6
480—630 0.8 0.6
670—1000 0.8 0.8
0.8
1120—1250 1.0 1.0
1.0
1320—2000 1.2 1.0
1.2
2500—4000 1.2
1.2
1.2
7.2) Pipeline Installation
7.2.1 When the pipeline and its accessories pass through wall, board and roof, holes should
be reserved in advance, and the dimension and location should meet the design demand.
7.2.2 The configure of the spot pipeline connection should not reduce its valid section.
7.2.3 The hanger can’t be set at the air-outlet, valve, and examination-port and automatic
control machine. And the suspender isn’t suitable to be fixed at the flange.
7.2.4 The configure of the spot pipeline connection should not reduce its valid section.
Horizontal installation
Vertical installation
Unconcealed
I
ll i
δ
≤3mm/m
Δ
≤20mm
δ
≤2mm/m
Δ
≤20mm
Concealed Installation
Installation correct, no obvious tolerance
δ
—tolerance /meter
Δ
—total tolerance
7.2.5 The hanger of insulated pipeline should set outside the insulation layer and can’t injure
the insulation layer.
Summary of Contents for R-410A
Page 103: ...Wall mount 102 Part 4 2 Wall Mounted...
Page 113: ...Wall mount 112 4 Dimensions 4 1 YDS 22 36EC 4 2 YDS 45 56EC...
Page 115: ...Wall mount 114 5 Piping Diagrams 5 1 YDS 22 56EC 5 2 YDS 22 56HC...
Page 116: ...Wall mount 115 6 Wiring diagrams 6 1 YDS 22 36EC 6 2 YDS 45 56EC...
Page 117: ...Wall mount 116 6 3 YDS 22 56HC...
Page 118: ...Wall mount 117 7 Sound level 7 1 Test condition 7 2 Noise spectrums YDS 22 36EC HC...
Page 119: ...Wall mount 118 YDS 45 56EC HC...
Page 120: ...Wall mount 119 8 Velocity temperature distribution Discharge angle 70...