(3) High efficiency
EER is up to 3.2.
(4) Long & single piping system
Digital scroll system is the only system that is free of oil separator and oil recycling
equipment. In the loading state, the speed of the refrigerant is enough to move oil back to the
compressor.
For 28Kw system, the maximum Pipe length between indoor unit and outdoor unit is
150m, the max. Height difference between indoor unit and outdoor unit is 50m, the max. Height
difference between indoor units is 15m.
For 10kw, 14kw system, the maximum Pipe length between indoor unit and outdoor unit
is 70m, the max. Height difference between indoor unit and outdoor unit is 20m, the max.
Height difference between indoor units is 8m.